Kabeltværsnit for 15 Ampere ved 90 Meter (230V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 15 A over 90 m ved 230V.

Copper Cable (≤3% Drop)10 mm²Drop: 5.78V (2.51%)
Aluminum Cable (≤3% Drop)16 mm²Drop: 5.96V (2.59%)
Voltage at Load224.2 VLine Loss: 86.7 W
Max Power & Breaker3.45 kW15A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 15A at 90m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A38.52 V (16.75%)191.5 V63.54 V (27.63%)577.8 WDrop High
2.5 mm²24 A18 A23.11 V (10.05%)206.9 V38.12 V (16.58%)346.7 WDrop High
4 mm²32 A25 A14.45 V (6.28%)215.6 V23.83 V (10.36%)216.7 WDrop High
6 mm²41 A32 A9.63 V (4.19%)220.4 V15.88 V (6.91%)144.5 W~ ≤5%
10 mm²57 A44 A5.78 V (2.51%)224.2 V9.53 V (4.14%)86.7 W✓ OK (≤3%)
16 mm²76 A59 A3.61 V (1.57%)226.4 V5.96 V (2.59%)54.2 W✓ OK (≤3%)
25 mm²101 A78 A2.31 V (1.0%)227.7 V3.81 V (1.66%)34.7 W✓ OK (≤3%)
35 mm²125 A97 A1.65 V (0.72%)228.3 V2.72 V (1.18%)24.8 W✓ OK (≤3%)
50 mm²151 A118 A1.16 V (0.5%)228.8 V1.91 V (0.83%)17.3 W✓ OK (≤3%)
70 mm²192 A150 A0.83 V (0.36%)229.2 V1.36 V (0.59%)12.4 W✓ OK (≤3%)
95 mm²232 A181 A0.61 V (0.26%)229.4 V1.0 V (0.44%)9.1 W✓ OK (≤3%)
120 mm²269 A210 A0.48 V (0.21%)229.5 V0.79 V (0.35%)7.2 W✓ OK (≤3%)
150 mm²309 A241 A0.39 V (0.17%)229.6 V0.64 V (0.28%)5.8 W✓ OK (≤3%)
185 mm²353 A275 A0.31 V (0.14%)229.7 V0.52 V (0.22%)4.7 W✓ OK (≤3%)
240 mm²415 A324 A0.24 V (0.1%)229.8 V0.4 V (0.17%)3.6 W✓ OK (≤3%)
300 mm²477 A372 A0.19 V (0.08%)229.8 V0.32 V (0.14%)2.9 W✓ OK (≤3%)
400 mm²570 A445 A0.14 V (0.06%)229.9 V0.24 V (0.1%)2.2 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 15 Ampere ved 90 Meter (230V)

Hvilket kabeltværsnit kræves til 15A ved 90 meter (230V)?

Til 15 Ampere over 90 meter ved 230V anbefales 10 mm² kobberkabel (spændingsfald 5.78V / 2.51%).

Hvor mange kW svarer 15A ved 230V til?

Det svarer til 3.45 kW med en anbefalet sikring på 15A.