Kabeltværsnit for 16 Ampere ved 50 Meter (400V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 16 A over 50 m ved 400V.

Copper Cable (≤3% Drop)2.5 mm²Drop: 11.86V (2.97%)
Aluminum Cable (≤3% Drop)6 mm²Drop: 8.15V (2.04%)
Voltage at Load388.1 VLine Loss: 328.7 W
Max Power & Breaker11.09 kW16A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 16A at 50m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A19.77 V (4.94%)380.2 V32.61 V (8.15%)547.8 W~ ≤5%
2.5 mm²24 A18 A11.86 V (2.97%)388.1 V19.57 V (4.89%)328.7 W✓ OK (≤3%)
4 mm²32 A25 A7.41 V (1.85%)392.6 V12.23 V (3.06%)205.4 W✓ OK (≤3%)
6 mm²41 A32 A4.94 V (1.24%)395.1 V8.15 V (2.04%)137.0 W✓ OK (≤3%)
10 mm²57 A44 A2.97 V (0.74%)397.0 V4.89 V (1.22%)82.2 W✓ OK (≤3%)
16 mm²76 A59 A1.85 V (0.46%)398.1 V3.06 V (0.76%)51.4 W✓ OK (≤3%)
25 mm²101 A78 A1.19 V (0.3%)398.8 V1.96 V (0.49%)32.9 W✓ OK (≤3%)
35 mm²125 A97 A0.85 V (0.21%)399.2 V1.4 V (0.35%)23.5 W✓ OK (≤3%)
50 mm²151 A118 A0.59 V (0.15%)399.4 V0.98 V (0.24%)16.4 W✓ OK (≤3%)
70 mm²192 A150 A0.42 V (0.11%)399.6 V0.7 V (0.17%)11.7 W✓ OK (≤3%)
95 mm²232 A181 A0.31 V (0.08%)399.7 V0.51 V (0.13%)8.7 W✓ OK (≤3%)
120 mm²269 A210 A0.25 V (0.06%)399.8 V0.41 V (0.1%)6.8 W✓ OK (≤3%)
150 mm²309 A241 A0.2 V (0.05%)399.8 V0.33 V (0.08%)5.5 W✓ OK (≤3%)
185 mm²353 A275 A0.16 V (0.04%)399.8 V0.26 V (0.07%)4.4 W✓ OK (≤3%)
240 mm²415 A324 A0.12 V (0.03%)399.9 V0.2 V (0.05%)3.4 W✓ OK (≤3%)
300 mm²477 A372 A0.1 V (0.02%)399.9 V0.16 V (0.04%)2.7 W✓ OK (≤3%)
400 mm²570 A445 A0.07 V (0.02%)399.9 V0.12 V (0.03%)2.1 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 16 Ampere ved 50 Meter (400V)

Hvilket kabeltværsnit kræves til 16A ved 50 meter (400V)?

Til 16 Ampere over 50 meter ved 400V anbefales 2.5 mm² kobberkabel (spændingsfald 11.86V / 2.97%).

Hvor mange kW svarer 16A ved 400V til?

Det svarer til 11.09 kW med en anbefalet sikring på 16A.