Kabeltværsnit for 16 Ampere ved 400 Meter (400V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 16 A over 400 m ved 400V.

Copper Cable (≤3% Drop)25 mm²Drop: 9.49V (2.37%)
Aluminum Cable (≤3% Drop)35 mm²Drop: 11.18V (2.8%)
Voltage at Load390.5 VLine Loss: 263.0 W
Max Power & Breaker11.09 kW16A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 16A at 400m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A158.15 V (39.54%)241.9 V260.87 V (65.22%)4382.7 WDrop High
2.5 mm²24 A18 A94.89 V (23.72%)305.1 V156.52 V (39.13%)2629.6 WDrop High
4 mm²32 A25 A59.31 V (14.83%)340.7 V97.83 V (24.46%)1643.5 WDrop High
6 mm²41 A32 A39.54 V (9.88%)360.5 V65.22 V (16.3%)1095.7 WDrop High
10 mm²57 A44 A23.72 V (5.93%)376.3 V39.13 V (9.78%)657.4 WDrop High
16 mm²76 A59 A14.83 V (3.71%)385.2 V24.46 V (6.11%)410.9 W~ ≤5%
25 mm²101 A78 A9.49 V (2.37%)390.5 V15.65 V (3.91%)263.0 W✓ OK (≤3%)
35 mm²125 A97 A6.78 V (1.69%)393.2 V11.18 V (2.8%)187.8 W✓ OK (≤3%)
50 mm²151 A118 A4.74 V (1.19%)395.3 V7.83 V (1.96%)131.5 W✓ OK (≤3%)
70 mm²192 A150 A3.39 V (0.85%)396.6 V5.59 V (1.4%)93.9 W✓ OK (≤3%)
95 mm²232 A181 A2.5 V (0.62%)397.5 V4.12 V (1.03%)69.2 W✓ OK (≤3%)
120 mm²269 A210 A1.98 V (0.49%)398.0 V3.26 V (0.82%)54.8 W✓ OK (≤3%)
150 mm²309 A241 A1.58 V (0.4%)398.4 V2.61 V (0.65%)43.8 W✓ OK (≤3%)
185 mm²353 A275 A1.28 V (0.32%)398.7 V2.12 V (0.53%)35.5 W✓ OK (≤3%)
240 mm²415 A324 A0.99 V (0.25%)399.0 V1.63 V (0.41%)27.4 W✓ OK (≤3%)
300 mm²477 A372 A0.79 V (0.2%)399.2 V1.3 V (0.33%)21.9 W✓ OK (≤3%)
400 mm²570 A445 A0.59 V (0.15%)399.4 V0.98 V (0.24%)16.4 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 16 Ampere ved 400 Meter (400V)

Hvilket kabeltværsnit kræves til 16A ved 400 meter (400V)?

Til 16 Ampere over 400 meter ved 400V anbefales 25 mm² kobberkabel (spændingsfald 9.49V / 2.37%).

Hvor mange kW svarer 16A ved 400V til?

Det svarer til 11.09 kW med en anbefalet sikring på 16A.