Kabeltværsnit for 160 Ampere ved 15 Meter (230V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 160 A over 15 m ved 230V.

Copper Cable (≤3% Drop)70 mm²Drop: 1.47V (0.64%)
Aluminum Cable (≤3% Drop)95 mm²Drop: 1.78V (0.78%)
Voltage at Load228.5 VLine Loss: 234.8 W
Max Power & Breaker36.8 kW160A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 160A at 15m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A68.48 V (29.77%)161.5 V112.96 V (49.11%)10956.8 WDrop High
2.5 mm²24 A18 A41.09 V (17.86%)188.9 V67.78 V (29.47%)6574.1 WDrop High
4 mm²32 A25 A25.68 V (11.17%)204.3 V42.36 V (18.42%)4108.8 WDrop High
6 mm²41 A32 A17.12 V (7.44%)212.9 V28.24 V (12.28%)2739.2 WDrop High
10 mm²57 A44 A10.27 V (4.47%)219.7 V16.94 V (7.37%)1643.5 WDrop High
16 mm²76 A59 A6.42 V (2.79%)223.6 V10.59 V (4.6%)1027.2 WDrop High
25 mm²101 A78 A4.11 V (1.79%)225.9 V6.78 V (2.95%)657.4 WDrop High
35 mm²125 A97 A2.93 V (1.28%)227.1 V4.84 V (2.1%)469.6 WDrop High
50 mm²151 A118 A2.05 V (0.89%)227.9 V3.39 V (1.47%)328.7 WDrop High
70 mm²192 A150 A1.47 V (0.64%)228.5 V2.42 V (1.05%)234.8 W✓ OK (≤3%)
95 mm²232 A181 A1.08 V (0.47%)228.9 V1.78 V (0.78%)173.0 W✓ OK (≤3%)
120 mm²269 A210 A0.86 V (0.37%)229.1 V1.41 V (0.61%)137.0 W✓ OK (≤3%)
150 mm²309 A241 A0.68 V (0.3%)229.3 V1.13 V (0.49%)109.6 W✓ OK (≤3%)
185 mm²353 A275 A0.56 V (0.24%)229.4 V0.92 V (0.4%)88.8 W✓ OK (≤3%)
240 mm²415 A324 A0.43 V (0.19%)229.6 V0.71 V (0.31%)68.5 W✓ OK (≤3%)
300 mm²477 A372 A0.34 V (0.15%)229.7 V0.56 V (0.25%)54.8 W✓ OK (≤3%)
400 mm²570 A445 A0.26 V (0.11%)229.7 V0.42 V (0.18%)41.1 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 160 Ampere ved 15 Meter (230V)

Hvilket kabeltværsnit kræves til 160A ved 15 meter (230V)?

Til 160 Ampere over 15 meter ved 230V anbefales 70 mm² kobberkabel (spændingsfald 1.47V / 0.64%).

Hvor mange kW svarer 160A ved 230V til?

Det svarer til 36.8 kW med en anbefalet sikring på 160A.