Kabeltværsnit for 160 Ampere ved 40 Meter (230V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 160 A over 40 m ved 230V.

Copper Cable (≤3% Drop)70 mm²Drop: 3.91V (1.7%)
Aluminum Cable (≤3% Drop)95 mm²Drop: 4.76V (2.07%)
Voltage at Load226.1 VLine Loss: 626.1 W
Max Power & Breaker36.8 kW160A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 160A at 40m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A182.61 V (79.4%)47.4 V301.23 V (130.97%)29218.1 WDrop High
2.5 mm²24 A18 A109.57 V (47.64%)120.4 V180.74 V (78.58%)17530.9 WDrop High
4 mm²32 A25 A68.48 V (29.77%)161.5 V112.96 V (49.11%)10956.8 WDrop High
6 mm²41 A32 A45.65 V (19.85%)184.3 V75.31 V (32.74%)7304.5 WDrop High
10 mm²57 A44 A27.39 V (11.91%)202.6 V45.18 V (19.65%)4382.7 WDrop High
16 mm²76 A59 A17.12 V (7.44%)212.9 V28.24 V (12.28%)2739.2 WDrop High
25 mm²101 A78 A10.96 V (4.76%)219.0 V18.07 V (7.86%)1753.1 WDrop High
35 mm²125 A97 A7.83 V (3.4%)222.2 V12.91 V (5.61%)1252.2 WDrop High
50 mm²151 A118 A5.48 V (2.38%)224.5 V9.04 V (3.93%)876.5 WDrop High
70 mm²192 A150 A3.91 V (1.7%)226.1 V6.45 V (2.81%)626.1 W✓ OK (≤3%)
95 mm²232 A181 A2.88 V (1.25%)227.1 V4.76 V (2.07%)461.3 W✓ OK (≤3%)
120 mm²269 A210 A2.28 V (0.99%)227.7 V3.77 V (1.64%)365.2 W✓ OK (≤3%)
150 mm²309 A241 A1.83 V (0.79%)228.2 V3.01 V (1.31%)292.2 W✓ OK (≤3%)
185 mm²353 A275 A1.48 V (0.64%)228.5 V2.44 V (1.06%)236.9 W✓ OK (≤3%)
240 mm²415 A324 A1.14 V (0.5%)228.9 V1.88 V (0.82%)182.6 W✓ OK (≤3%)
300 mm²477 A372 A0.91 V (0.4%)229.1 V1.51 V (0.65%)146.1 W✓ OK (≤3%)
400 mm²570 A445 A0.68 V (0.3%)229.3 V1.13 V (0.49%)109.6 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 160 Ampere ved 40 Meter (230V)

Hvilket kabeltværsnit kræves til 160A ved 40 meter (230V)?

Til 160 Ampere over 40 meter ved 230V anbefales 70 mm² kobberkabel (spændingsfald 3.91V / 1.7%).

Hvor mange kW svarer 160A ved 230V til?

Det svarer til 36.8 kW med en anbefalet sikring på 160A.