⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabeltværsnit for 40 Ampere ved 70 Meter (400V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 40 A over 70 m ved 400V.

Copper Cable (≤3% Drop)10 mm²Drop: 10.38V (2.59%)
Aluminum Cable (≤3% Drop)16 mm²Drop: 10.7V (2.67%)
Voltage at Load389.6 VLine Loss: 719.0 W
Max Power & Breaker27.71 kW40A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 40A at 70m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A69.19 V (17.3%)330.8 V114.13 V (28.53%)4793.6 WDrop High
2.5 mm²24 A18 A41.51 V (10.38%)358.5 V68.48 V (17.12%)2876.2 WDrop High
4 mm²32 A25 A25.95 V (6.49%)374.1 V42.8 V (10.7%)1797.6 WDrop High
6 mm²41 A32 A17.3 V (4.32%)382.7 V28.53 V (7.13%)1198.4 W~ ≤5%
10 mm²57 A44 A10.38 V (2.59%)389.6 V17.12 V (4.28%)719.0 W✓ OK (≤3%)
16 mm²76 A59 A6.49 V (1.62%)393.5 V10.7 V (2.67%)449.4 W✓ OK (≤3%)
25 mm²101 A78 A4.15 V (1.04%)395.8 V6.85 V (1.71%)287.6 W✓ OK (≤3%)
35 mm²125 A97 A2.97 V (0.74%)397.0 V4.89 V (1.22%)205.4 W✓ OK (≤3%)
50 mm²151 A118 A2.08 V (0.52%)397.9 V3.42 V (0.86%)143.8 W✓ OK (≤3%)
70 mm²192 A150 A1.48 V (0.37%)398.5 V2.45 V (0.61%)102.7 W✓ OK (≤3%)
95 mm²232 A181 A1.09 V (0.27%)398.9 V1.8 V (0.45%)75.7 W✓ OK (≤3%)
120 mm²269 A210 A0.86 V (0.22%)399.1 V1.43 V (0.36%)59.9 W✓ OK (≤3%)
150 mm²309 A241 A0.69 V (0.17%)399.3 V1.14 V (0.29%)47.9 W✓ OK (≤3%)
185 mm²353 A275 A0.56 V (0.14%)399.4 V0.93 V (0.23%)38.9 W✓ OK (≤3%)
240 mm²415 A324 A0.43 V (0.11%)399.6 V0.71 V (0.18%)30.0 W✓ OK (≤3%)
300 mm²477 A372 A0.35 V (0.09%)399.7 V0.57 V (0.14%)24.0 W✓ OK (≤3%)
400 mm²570 A445 A0.26 V (0.06%)399.7 V0.43 V (0.11%)18.0 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 40 Ampere ved 70 Meter (400V)

Hvilket kabeltværsnit kræves til 40A ved 70 meter (400V)?

Til 40 Ampere over 70 meter ved 400V anbefales 10 mm² kobberkabel (spændingsfald 10.38V / 2.59%).

Hvor mange kW svarer 40A ved 400V til?

Det svarer til 27.71 kW med en anbefalet sikring på 40A.