Kabeltværsnit for 175 Ampere ved 15 Meter (400V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 175 A over 15 m ved 400V.

Copper Cable (≤3% Drop)70 mm²Drop: 1.39V (0.35%)
Aluminum Cable (≤3% Drop)95 mm²Drop: 1.69V (0.42%)
Voltage at Load398.6 VLine Loss: 421.3 W
Max Power & Breaker121.24 kW175A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 175A at 15m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A64.87 V (16.22%)335.1 V107.0 V (26.75%)19661.2 WDrop High
2.5 mm²24 A18 A38.92 V (9.73%)361.1 V64.2 V (16.05%)11796.8 WDrop High
4 mm²32 A25 A24.32 V (6.08%)375.7 V40.12 V (10.03%)7373.0 WDrop High
6 mm²41 A32 A16.22 V (4.05%)383.8 V26.75 V (6.69%)4915.3 WDrop High
10 mm²57 A44 A9.73 V (2.43%)390.3 V16.05 V (4.01%)2949.2 WDrop High
16 mm²76 A59 A6.08 V (1.52%)393.9 V10.03 V (2.51%)1843.2 WDrop High
25 mm²101 A78 A3.89 V (0.97%)396.1 V6.42 V (1.6%)1179.7 WDrop High
35 mm²125 A97 A2.78 V (0.69%)397.2 V4.59 V (1.15%)842.6 WDrop High
50 mm²151 A118 A1.95 V (0.49%)398.1 V3.21 V (0.8%)589.8 WDrop High
70 mm²192 A150 A1.39 V (0.35%)398.6 V2.29 V (0.57%)421.3 W✓ OK (≤3%)
95 mm²232 A181 A1.02 V (0.26%)399.0 V1.69 V (0.42%)310.4 W✓ OK (≤3%)
120 mm²269 A210 A0.81 V (0.2%)399.2 V1.34 V (0.33%)245.8 W✓ OK (≤3%)
150 mm²309 A241 A0.65 V (0.16%)399.4 V1.07 V (0.27%)196.6 W✓ OK (≤3%)
185 mm²353 A275 A0.53 V (0.13%)399.5 V0.87 V (0.22%)159.4 W✓ OK (≤3%)
240 mm²415 A324 A0.41 V (0.1%)399.6 V0.67 V (0.17%)122.9 W✓ OK (≤3%)
300 mm²477 A372 A0.32 V (0.08%)399.7 V0.53 V (0.13%)98.3 W✓ OK (≤3%)
400 mm²570 A445 A0.24 V (0.06%)399.8 V0.4 V (0.1%)73.7 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 175 Ampere ved 15 Meter (400V)

Hvilket kabeltværsnit kræves til 175A ved 15 meter (400V)?

Til 175 Ampere over 15 meter ved 400V anbefales 70 mm² kobberkabel (spændingsfald 1.39V / 0.35%).

Hvor mange kW svarer 175A ved 400V til?

Det svarer til 121.24 kW med en anbefalet sikring på 175A.