⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabeltværsnit for 175 Ampere ved 40 Meter (400V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 175 A over 40 m ved 400V.

Copper Cable (≤3% Drop)70 mm²Drop: 3.71V (0.93%)
Aluminum Cable (≤3% Drop)95 mm²Drop: 4.51V (1.13%)
Voltage at Load396.3 VLine Loss: 1123.5 W
Max Power & Breaker121.24 kW175A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 175A at 40m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A172.97 V (43.24%)227.0 V285.33 V (71.33%)52430.0 WDrop High
2.5 mm²24 A18 A103.78 V (25.95%)296.2 V171.2 V (42.8%)31458.0 WDrop High
4 mm²32 A25 A64.87 V (16.22%)335.1 V107.0 V (26.75%)19661.2 WDrop High
6 mm²41 A32 A43.24 V (10.81%)356.8 V71.33 V (17.83%)13107.5 WDrop High
10 mm²57 A44 A25.95 V (6.49%)374.1 V42.8 V (10.7%)7864.5 WDrop High
16 mm²76 A59 A16.22 V (4.05%)383.8 V26.75 V (6.69%)4915.3 WDrop High
25 mm²101 A78 A10.38 V (2.59%)389.6 V17.12 V (4.28%)3145.8 WDrop High
35 mm²125 A97 A7.41 V (1.85%)392.6 V12.23 V (3.06%)2247.0 WDrop High
50 mm²151 A118 A5.19 V (1.3%)394.8 V8.56 V (2.14%)1572.9 WDrop High
70 mm²192 A150 A3.71 V (0.93%)396.3 V6.11 V (1.53%)1123.5 W✓ OK (≤3%)
95 mm²232 A181 A2.73 V (0.68%)397.3 V4.51 V (1.13%)827.8 W✓ OK (≤3%)
120 mm²269 A210 A2.16 V (0.54%)397.8 V3.57 V (0.89%)655.4 W✓ OK (≤3%)
150 mm²309 A241 A1.73 V (0.43%)398.3 V2.85 V (0.71%)524.3 W✓ OK (≤3%)
185 mm²353 A275 A1.4 V (0.35%)398.6 V2.31 V (0.58%)425.1 W✓ OK (≤3%)
240 mm²415 A324 A1.08 V (0.27%)398.9 V1.78 V (0.45%)327.7 W✓ OK (≤3%)
300 mm²477 A372 A0.86 V (0.22%)399.1 V1.43 V (0.36%)262.1 W✓ OK (≤3%)
400 mm²570 A445 A0.65 V (0.16%)399.4 V1.07 V (0.27%)196.6 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 175 Ampere ved 40 Meter (400V)

Hvilket kabeltværsnit kræves til 175A ved 40 meter (400V)?

Til 175 Ampere over 40 meter ved 400V anbefales 70 mm² kobberkabel (spændingsfald 3.71V / 0.93%).

Hvor mange kW svarer 175A ved 400V til?

Det svarer til 121.24 kW med en anbefalet sikring på 175A.