Kabeltværsnit for 175 Ampere ved 70 Meter (400V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 175 A over 70 m ved 400V.

Copper Cable (≤3% Drop)70 mm²Drop: 6.49V (1.62%)
Aluminum Cable (≤3% Drop)95 mm²Drop: 7.88V (1.97%)
Voltage at Load393.5 VLine Loss: 1966.1 W
Max Power & Breaker121.24 kW175A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 175A at 70m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A302.7 V (75.68%)97.3 V499.32 V (124.83%)91752.5 WDrop High
2.5 mm²24 A18 A181.62 V (45.41%)218.4 V299.59 V (74.9%)55051.5 WDrop High
4 mm²32 A25 A113.51 V (28.38%)286.5 V187.25 V (46.81%)34407.2 WDrop High
6 mm²41 A32 A75.68 V (18.92%)324.3 V124.83 V (31.21%)22938.1 WDrop High
10 mm²57 A44 A45.41 V (11.35%)354.6 V74.9 V (18.72%)13762.9 WDrop High
16 mm²76 A59 A28.38 V (7.09%)371.6 V46.81 V (11.7%)8601.8 WDrop High
25 mm²101 A78 A18.16 V (4.54%)381.8 V29.96 V (7.49%)5505.2 WDrop High
35 mm²125 A97 A12.97 V (3.24%)387.0 V21.4 V (5.35%)3932.2 WDrop High
50 mm²151 A118 A9.08 V (2.27%)390.9 V14.98 V (3.74%)2752.6 WDrop High
70 mm²192 A150 A6.49 V (1.62%)393.5 V10.7 V (2.67%)1966.1 W✓ OK (≤3%)
95 mm²232 A181 A4.78 V (1.19%)395.2 V7.88 V (1.97%)1448.7 W✓ OK (≤3%)
120 mm²269 A210 A3.78 V (0.95%)396.2 V6.24 V (1.56%)1146.9 W✓ OK (≤3%)
150 mm²309 A241 A3.03 V (0.76%)397.0 V4.99 V (1.25%)917.5 W✓ OK (≤3%)
185 mm²353 A275 A2.45 V (0.61%)397.5 V4.05 V (1.01%)743.9 W✓ OK (≤3%)
240 mm²415 A324 A1.89 V (0.47%)398.1 V3.12 V (0.78%)573.5 W✓ OK (≤3%)
300 mm²477 A372 A1.51 V (0.38%)398.5 V2.5 V (0.62%)458.8 W✓ OK (≤3%)
400 mm²570 A445 A1.14 V (0.28%)398.9 V1.87 V (0.47%)344.1 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 175 Ampere ved 70 Meter (400V)

Hvilket kabeltværsnit kræves til 175A ved 70 meter (400V)?

Til 175 Ampere over 70 meter ved 400V anbefales 70 mm² kobberkabel (spændingsfald 6.49V / 1.62%).

Hvor mange kW svarer 175A ved 400V til?

Det svarer til 121.24 kW med en anbefalet sikring på 175A.