Kabeltværsnit for 175 Ampere ved 150 Meter (230V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 175 A over 150 m ved 230V.

Copper Cable (≤3% Drop)185 mm²Drop: 6.07V (2.64%)
Aluminum Cable (≤3% Drop)300 mm²Drop: 6.18V (2.69%)
Voltage at Load223.9 VLine Loss: 1062.8 W
Max Power & Breaker40.25 kW175A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 175A at 150m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A749.0 V (325.65%)0.0 V1235.5 V (537.17%)131075.0 WDrop High
2.5 mm²24 A18 A449.4 V (195.39%)0.0 V741.3 V (322.3%)78645.0 WDrop High
4 mm²32 A25 A280.88 V (122.12%)0.0 V463.31 V (201.44%)49153.1 WDrop High
6 mm²41 A32 A187.25 V (81.41%)42.8 V308.88 V (134.29%)32768.8 WDrop High
10 mm²57 A44 A112.35 V (48.85%)117.6 V185.32 V (80.58%)19661.2 WDrop High
16 mm²76 A59 A70.22 V (30.53%)159.8 V115.83 V (50.36%)12288.3 WDrop High
25 mm²101 A78 A44.94 V (19.54%)185.1 V74.13 V (32.23%)7864.5 WDrop High
35 mm²125 A97 A32.1 V (13.96%)197.9 V52.95 V (23.02%)5617.5 WDrop High
50 mm²151 A118 A22.47 V (9.77%)207.5 V37.06 V (16.12%)3932.2 WDrop High
70 mm²192 A150 A16.05 V (6.98%)213.9 V26.47 V (11.51%)2808.7 WDrop High
95 mm²232 A181 A11.83 V (5.14%)218.2 V19.51 V (8.48%)2069.6 WDrop High
120 mm²269 A210 A9.36 V (4.07%)220.6 V15.44 V (6.71%)1638.4 W~ ≤5%
150 mm²309 A241 A7.49 V (3.26%)222.5 V12.35 V (5.37%)1310.8 W~ ≤5%
185 mm²353 A275 A6.07 V (2.64%)223.9 V10.02 V (4.36%)1062.8 W✓ OK (≤3%)
240 mm²415 A324 A4.68 V (2.04%)225.3 V7.72 V (3.36%)819.2 W✓ OK (≤3%)
300 mm²477 A372 A3.74 V (1.63%)226.3 V6.18 V (2.69%)655.4 W✓ OK (≤3%)
400 mm²570 A445 A2.81 V (1.22%)227.2 V4.63 V (2.01%)491.5 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 175 Ampere ved 150 Meter (230V)

Hvilket kabeltværsnit kræves til 175A ved 150 meter (230V)?

Til 175 Ampere over 150 meter ved 230V anbefales 185 mm² kobberkabel (spændingsfald 6.07V / 2.64%).

Hvor mange kW svarer 175A ved 230V til?

Det svarer til 40.25 kW med en anbefalet sikring på 175A.