Kabeltværsnit for 175 Ampere ved 10 Meter (230V)
Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 175 A over 10 m ved 230V.
Copper Cable (≤3% Drop)70 mm²Drop: 1.07V (0.47%)
Aluminum Cable (≤3% Drop)95 mm²Drop: 1.3V (0.57%)
Voltage at Load228.9 VLine Loss: 187.2 W
Max Power & Breaker40.25 kW175A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 175A at 10m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 49.93 V (21.71%) | 180.1 V | 82.37 V (35.81%) | 8738.3 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 29.96 V (13.03%) | 200.0 V | 49.42 V (21.49%) | 5243.0 W | Drop High |
| 4 mm² | 32 A | 25 A | 18.72 V (8.14%) | 211.3 V | 30.89 V (13.43%) | 3276.9 W | Drop High |
| 6 mm² | 41 A | 32 A | 12.48 V (5.43%) | 217.5 V | 20.59 V (8.95%) | 2184.6 W | Drop High |
| 10 mm² | 57 A | 44 A | 7.49 V (3.26%) | 222.5 V | 12.35 V (5.37%) | 1310.8 W | Drop High |
| 16 mm² | 76 A | 59 A | 4.68 V (2.04%) | 225.3 V | 7.72 V (3.36%) | 819.2 W | Drop High |
| 25 mm² | 101 A | 78 A | 3.0 V (1.3%) | 227.0 V | 4.94 V (2.15%) | 524.3 W | Drop High |
| 35 mm² | 125 A | 97 A | 2.14 V (0.93%) | 227.9 V | 3.53 V (1.53%) | 374.5 W | Drop High |
| 50 mm² | 151 A | 118 A | 1.5 V (0.65%) | 228.5 V | 2.47 V (1.07%) | 262.1 W | Drop High |
| 70 mm² | 192 A | 150 A | 1.07 V (0.47%) | 228.9 V | 1.76 V (0.77%) | 187.2 W | ✓ OK (≤3%) |
| 95 mm² | 232 A | 181 A | 0.79 V (0.34%) | 229.2 V | 1.3 V (0.57%) | 138.0 W | ✓ OK (≤3%) |
| 120 mm² | 269 A | 210 A | 0.62 V (0.27%) | 229.4 V | 1.03 V (0.45%) | 109.2 W | ✓ OK (≤3%) |
| 150 mm² | 309 A | 241 A | 0.5 V (0.22%) | 229.5 V | 0.82 V (0.36%) | 87.4 W | ✓ OK (≤3%) |
| 185 mm² | 353 A | 275 A | 0.4 V (0.18%) | 229.6 V | 0.67 V (0.29%) | 70.9 W | ✓ OK (≤3%) |
| 240 mm² | 415 A | 324 A | 0.31 V (0.14%) | 229.7 V | 0.51 V (0.22%) | 54.6 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 0.25 V (0.11%) | 229.8 V | 0.41 V (0.18%) | 43.7 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 0.19 V (0.08%) | 229.8 V | 0.31 V (0.13%) | 32.8 W | ✓ OK (≤3%) |
FAQ — Kabeltværsnit for 175 Ampere ved 10 Meter (230V)
Hvilket kabeltværsnit kræves til 175A ved 10 meter (230V)?
Til 175 Ampere over 10 meter ved 230V anbefales 70 mm² kobberkabel (spændingsfald 1.07V / 0.47%).
Hvor mange kW svarer 175A ved 230V til?
Det svarer til 40.25 kW med en anbefalet sikring på 175A.
Related Lengths & Currents (230V)
175A · 5m (230V)175A · 15m (230V)175A · 20m (230V)175A · 25m (230V)175A · 30m (230V)175A · 35m (230V)175A · 40m (230V)175A · 45m (230V)175A · 50m (230V)175A · 60m (230V)175A · 70m (230V)10A · 10m (230V)16A · 10m (230V)20A · 10m (230V)25A · 10m (230V)32A · 10m (230V)40A · 10m (230V)50A · 10m (230V)63A · 10m (230V)80A · 10m (230V)100A · 10m (230V)125A · 10m (230V)160A · 10m (230V)200A · 10m (230V)