⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabeltværsnit for 175 Ampere ved 25 Meter (230V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 175 A over 25 m ved 230V.

Copper Cable (≤3% Drop)70 mm²Drop: 2.67V (1.16%)
Aluminum Cable (≤3% Drop)95 mm²Drop: 3.25V (1.41%)
Voltage at Load227.3 VLine Loss: 468.1 W
Max Power & Breaker40.25 kW175A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 175A at 25m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A124.83 V (54.28%)105.2 V205.92 V (89.53%)21845.8 WDrop High
2.5 mm²24 A18 A74.9 V (32.57%)155.1 V123.55 V (53.72%)13107.5 WDrop High
4 mm²32 A25 A46.81 V (20.35%)183.2 V77.22 V (33.57%)8192.2 WDrop High
6 mm²41 A32 A31.21 V (13.57%)198.8 V51.48 V (22.38%)5461.5 WDrop High
10 mm²57 A44 A18.72 V (8.14%)211.3 V30.89 V (13.43%)3276.9 WDrop High
16 mm²76 A59 A11.7 V (5.09%)218.3 V19.3 V (8.39%)2048.0 WDrop High
25 mm²101 A78 A7.49 V (3.26%)222.5 V12.35 V (5.37%)1310.7 WDrop High
35 mm²125 A97 A5.35 V (2.33%)224.7 V8.82 V (3.84%)936.2 WDrop High
50 mm²151 A118 A3.74 V (1.63%)226.3 V6.18 V (2.69%)655.4 WDrop High
70 mm²192 A150 A2.67 V (1.16%)227.3 V4.41 V (1.92%)468.1 W✓ OK (≤3%)
95 mm²232 A181 A1.97 V (0.86%)228.0 V3.25 V (1.41%)344.9 W✓ OK (≤3%)
120 mm²269 A210 A1.56 V (0.68%)228.4 V2.57 V (1.12%)273.1 W✓ OK (≤3%)
150 mm²309 A241 A1.25 V (0.54%)228.8 V2.06 V (0.9%)218.5 W✓ OK (≤3%)
185 mm²353 A275 A1.01 V (0.44%)229.0 V1.67 V (0.73%)177.1 W✓ OK (≤3%)
240 mm²415 A324 A0.78 V (0.34%)229.2 V1.29 V (0.56%)136.5 W✓ OK (≤3%)
300 mm²477 A372 A0.62 V (0.27%)229.4 V1.03 V (0.45%)109.2 W✓ OK (≤3%)
400 mm²570 A445 A0.47 V (0.2%)229.5 V0.77 V (0.34%)81.9 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 175 Ampere ved 25 Meter (230V)

Hvilket kabeltværsnit kræves til 175A ved 25 meter (230V)?

Til 175 Ampere over 25 meter ved 230V anbefales 70 mm² kobberkabel (spændingsfald 2.67V / 1.16%).

Hvor mange kW svarer 175A ved 230V til?

Det svarer til 40.25 kW med en anbefalet sikring på 175A.