Kabeltværsnit for 175 Ampere ved 30 Meter (230V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 175 A over 30 m ved 230V.

Copper Cable (≤3% Drop)70 mm²Drop: 3.21V (1.4%)
Aluminum Cable (≤3% Drop)95 mm²Drop: 3.9V (1.7%)
Voltage at Load226.8 VLine Loss: 561.8 W
Max Power & Breaker40.25 kW175A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 175A at 30m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A149.8 V (65.13%)80.2 V247.1 V (107.43%)26215.0 WDrop High
2.5 mm²24 A18 A89.88 V (39.08%)140.1 V148.26 V (64.46%)15729.0 WDrop High
4 mm²32 A25 A56.18 V (24.42%)173.8 V92.66 V (40.29%)9830.6 WDrop High
6 mm²41 A32 A37.45 V (16.28%)192.6 V61.77 V (26.86%)6553.8 WDrop High
10 mm²57 A44 A22.47 V (9.77%)207.5 V37.06 V (16.12%)3932.3 WDrop High
16 mm²76 A59 A14.04 V (6.11%)216.0 V23.17 V (10.07%)2457.7 WDrop High
25 mm²101 A78 A8.99 V (3.91%)221.0 V14.83 V (6.45%)1572.9 WDrop High
35 mm²125 A97 A6.42 V (2.79%)223.6 V10.59 V (4.6%)1123.5 WDrop High
50 mm²151 A118 A4.49 V (1.95%)225.5 V7.41 V (3.22%)786.5 WDrop High
70 mm²192 A150 A3.21 V (1.4%)226.8 V5.29 V (2.3%)561.8 W✓ OK (≤3%)
95 mm²232 A181 A2.37 V (1.03%)227.6 V3.9 V (1.7%)413.9 W✓ OK (≤3%)
120 mm²269 A210 A1.87 V (0.81%)228.1 V3.09 V (1.34%)327.7 W✓ OK (≤3%)
150 mm²309 A241 A1.5 V (0.65%)228.5 V2.47 V (1.07%)262.1 W✓ OK (≤3%)
185 mm²353 A275 A1.21 V (0.53%)228.8 V2.0 V (0.87%)212.6 W✓ OK (≤3%)
240 mm²415 A324 A0.94 V (0.41%)229.1 V1.54 V (0.67%)163.8 W✓ OK (≤3%)
300 mm²477 A372 A0.75 V (0.33%)229.3 V1.24 V (0.54%)131.1 W✓ OK (≤3%)
400 mm²570 A445 A0.56 V (0.24%)229.4 V0.93 V (0.4%)98.3 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 175 Ampere ved 30 Meter (230V)

Hvilket kabeltværsnit kræves til 175A ved 30 meter (230V)?

Til 175 Ampere over 30 meter ved 230V anbefales 70 mm² kobberkabel (spændingsfald 3.21V / 1.4%).

Hvor mange kW svarer 175A ved 230V til?

Det svarer til 40.25 kW med en anbefalet sikring på 175A.