Kabeltværsnit for 20 Ampere ved 40 Meter (230V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 20 A over 40 m ved 230V.

Copper Cable (≤3% Drop)6 mm²Drop: 5.71V (2.48%)
Aluminum Cable (≤3% Drop)10 mm²Drop: 5.65V (2.46%)
Voltage at Load224.3 VLine Loss: 114.1 W
Max Power & Breaker4.6 kW20A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 20A at 40m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A22.83 V (9.92%)207.2 V37.65 V (16.37%)456.5 WDrop High
2.5 mm²24 A18 A13.7 V (5.95%)216.3 V22.59 V (9.82%)273.9 WDrop High
4 mm²32 A25 A8.56 V (3.72%)221.4 V14.12 V (6.14%)171.2 W~ ≤5%
6 mm²41 A32 A5.71 V (2.48%)224.3 V9.41 V (4.09%)114.1 W✓ OK (≤3%)
10 mm²57 A44 A3.42 V (1.49%)226.6 V5.65 V (2.46%)68.5 W✓ OK (≤3%)
16 mm²76 A59 A2.14 V (0.93%)227.9 V3.53 V (1.53%)42.8 W✓ OK (≤3%)
25 mm²101 A78 A1.37 V (0.6%)228.6 V2.26 V (0.98%)27.4 W✓ OK (≤3%)
35 mm²125 A97 A0.98 V (0.43%)229.0 V1.61 V (0.7%)19.6 W✓ OK (≤3%)
50 mm²151 A118 A0.68 V (0.3%)229.3 V1.13 V (0.49%)13.7 W✓ OK (≤3%)
70 mm²192 A150 A0.49 V (0.21%)229.5 V0.81 V (0.35%)9.8 W✓ OK (≤3%)
95 mm²232 A181 A0.36 V (0.16%)229.6 V0.59 V (0.26%)7.2 W✓ OK (≤3%)
120 mm²269 A210 A0.29 V (0.12%)229.7 V0.47 V (0.2%)5.7 W✓ OK (≤3%)
150 mm²309 A241 A0.23 V (0.1%)229.8 V0.38 V (0.16%)4.6 W✓ OK (≤3%)
185 mm²353 A275 A0.19 V (0.08%)229.8 V0.31 V (0.13%)3.7 W✓ OK (≤3%)
240 mm²415 A324 A0.14 V (0.06%)229.9 V0.24 V (0.1%)2.9 W✓ OK (≤3%)
300 mm²477 A372 A0.11 V (0.05%)229.9 V0.19 V (0.08%)2.3 W✓ OK (≤3%)
400 mm²570 A445 A0.09 V (0.04%)229.9 V0.14 V (0.06%)1.7 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 20 Ampere ved 40 Meter (230V)

Hvilket kabeltværsnit kræves til 20A ved 40 meter (230V)?

Til 20 Ampere over 40 meter ved 230V anbefales 6 mm² kobberkabel (spændingsfald 5.71V / 2.48%).

Hvor mange kW svarer 20A ved 230V til?

Det svarer til 4.6 kW med en anbefalet sikring på 20A.