Kabeltværsnit for 20 Ampere ved 15 Meter (230V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 20 A over 15 m ved 230V.

Copper Cable (≤3% Drop)2.5 mm²Drop: 5.14V (2.23%)
Aluminum Cable (≤3% Drop)4 mm²Drop: 5.29V (2.3%)
Voltage at Load224.9 VLine Loss: 102.7 W
Max Power & Breaker4.6 kW20A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 20A at 15m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A8.56 V (3.72%)221.4 V14.12 V (6.14%)171.2 WDrop High
2.5 mm²24 A18 A5.14 V (2.23%)224.9 V8.47 V (3.68%)102.7 W✓ OK (≤3%)
4 mm²32 A25 A3.21 V (1.4%)226.8 V5.29 V (2.3%)64.2 W✓ OK (≤3%)
6 mm²41 A32 A2.14 V (0.93%)227.9 V3.53 V (1.53%)42.8 W✓ OK (≤3%)
10 mm²57 A44 A1.28 V (0.56%)228.7 V2.12 V (0.92%)25.7 W✓ OK (≤3%)
16 mm²76 A59 A0.8 V (0.35%)229.2 V1.32 V (0.58%)16.1 W✓ OK (≤3%)
25 mm²101 A78 A0.51 V (0.22%)229.5 V0.85 V (0.37%)10.3 W✓ OK (≤3%)
35 mm²125 A97 A0.37 V (0.16%)229.6 V0.61 V (0.26%)7.3 W✓ OK (≤3%)
50 mm²151 A118 A0.26 V (0.11%)229.7 V0.42 V (0.18%)5.1 W✓ OK (≤3%)
70 mm²192 A150 A0.18 V (0.08%)229.8 V0.3 V (0.13%)3.7 W✓ OK (≤3%)
95 mm²232 A181 A0.14 V (0.06%)229.9 V0.22 V (0.1%)2.7 W✓ OK (≤3%)
120 mm²269 A210 A0.11 V (0.05%)229.9 V0.18 V (0.08%)2.1 W✓ OK (≤3%)
150 mm²309 A241 A0.09 V (0.04%)229.9 V0.14 V (0.06%)1.7 W✓ OK (≤3%)
185 mm²353 A275 A0.07 V (0.03%)229.9 V0.11 V (0.05%)1.4 W✓ OK (≤3%)
240 mm²415 A324 A0.05 V (0.02%)229.9 V0.09 V (0.04%)1.1 W✓ OK (≤3%)
300 mm²477 A372 A0.04 V (0.02%)230.0 V0.07 V (0.03%)0.9 W✓ OK (≤3%)
400 mm²570 A445 A0.03 V (0.01%)230.0 V0.05 V (0.02%)0.6 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 20 Ampere ved 15 Meter (230V)

Hvilket kabeltværsnit kræves til 20A ved 15 meter (230V)?

Til 20 Ampere over 15 meter ved 230V anbefales 2.5 mm² kobberkabel (spændingsfald 5.14V / 2.23%).

Hvor mange kW svarer 20A ved 230V til?

Det svarer til 4.6 kW med en anbefalet sikring på 20A.