Kabeltværsnit for 250 Ampere ved 45 Meter (230V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 250 A over 45 m ved 230V.

Copper Cable (≤3% Drop)120 mm²Drop: 4.01V (1.74%)
Aluminum Cable (≤3% Drop)185 mm²Drop: 4.29V (1.87%)
Voltage at Load226.0 VLine Loss: 1003.1 W
Max Power & Breaker57.5 kW250A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 250A at 45m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A321.0 V (139.57%)0.0 V529.5 V (230.22%)80250.0 WDrop High
2.5 mm²24 A18 A192.6 V (83.74%)37.4 V317.7 V (138.13%)48150.0 WDrop High
4 mm²32 A25 A120.38 V (52.34%)109.6 V198.56 V (86.33%)30093.8 WDrop High
6 mm²41 A32 A80.25 V (34.89%)149.8 V132.38 V (57.55%)20062.5 WDrop High
10 mm²57 A44 A48.15 V (20.93%)181.8 V79.42 V (34.53%)12037.5 WDrop High
16 mm²76 A59 A30.09 V (13.08%)199.9 V49.64 V (21.58%)7523.4 WDrop High
25 mm²101 A78 A19.26 V (8.37%)210.7 V31.77 V (13.81%)4815.0 WDrop High
35 mm²125 A97 A13.76 V (5.98%)216.2 V22.69 V (9.87%)3439.3 WDrop High
50 mm²151 A118 A9.63 V (4.19%)220.4 V15.88 V (6.91%)2407.5 WDrop High
70 mm²192 A150 A6.88 V (2.99%)223.1 V11.35 V (4.93%)1719.6 WDrop High
95 mm²232 A181 A5.07 V (2.2%)224.9 V8.36 V (3.64%)1267.1 WDrop High
120 mm²269 A210 A4.01 V (1.74%)226.0 V6.62 V (2.88%)1003.1 W✓ OK (≤3%)
150 mm²309 A241 A3.21 V (1.4%)226.8 V5.29 V (2.3%)802.5 W✓ OK (≤3%)
185 mm²353 A275 A2.6 V (1.13%)227.4 V4.29 V (1.87%)650.7 W✓ OK (≤3%)
240 mm²415 A324 A2.01 V (0.87%)228.0 V3.31 V (1.44%)501.6 W✓ OK (≤3%)
300 mm²477 A372 A1.6 V (0.7%)228.4 V2.65 V (1.15%)401.2 W✓ OK (≤3%)
400 mm²570 A445 A1.2 V (0.52%)228.8 V1.99 V (0.86%)300.9 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 250 Ampere ved 45 Meter (230V)

Hvilket kabeltværsnit kræves til 250A ved 45 meter (230V)?

Til 250 Ampere over 45 meter ved 230V anbefales 120 mm² kobberkabel (spændingsfald 4.01V / 1.74%).

Hvor mange kW svarer 250A ved 230V til?

Det svarer til 57.5 kW med en anbefalet sikring på 250A.