Kabeltværsnit for 250 Ampere ved 10 Meter (230V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 250 A over 10 m ved 230V.

Copper Cable (≤3% Drop)120 mm²Drop: 0.89V (0.39%)
Aluminum Cable (≤3% Drop)185 mm²Drop: 0.95V (0.41%)
Voltage at Load229.1 VLine Loss: 222.9 W
Max Power & Breaker57.5 kW250A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 250A at 10m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A71.33 V (31.01%)158.7 V117.67 V (51.16%)17833.3 WDrop High
2.5 mm²24 A18 A42.8 V (18.61%)187.2 V70.6 V (30.7%)10700.0 WDrop High
4 mm²32 A25 A26.75 V (11.63%)203.2 V44.12 V (19.18%)6687.5 WDrop High
6 mm²41 A32 A17.83 V (7.75%)212.2 V29.42 V (12.79%)4458.3 WDrop High
10 mm²57 A44 A10.7 V (4.65%)219.3 V17.65 V (7.67%)2675.0 WDrop High
16 mm²76 A59 A6.69 V (2.91%)223.3 V11.03 V (4.8%)1671.9 WDrop High
25 mm²101 A78 A4.28 V (1.86%)225.7 V7.06 V (3.07%)1070.0 WDrop High
35 mm²125 A97 A3.06 V (1.33%)226.9 V5.04 V (2.19%)764.3 WDrop High
50 mm²151 A118 A2.14 V (0.93%)227.9 V3.53 V (1.53%)535.0 WDrop High
70 mm²192 A150 A1.53 V (0.66%)228.5 V2.52 V (1.1%)382.1 WDrop High
95 mm²232 A181 A1.13 V (0.49%)228.9 V1.86 V (0.81%)281.6 WDrop High
120 mm²269 A210 A0.89 V (0.39%)229.1 V1.47 V (0.64%)222.9 W✓ OK (≤3%)
150 mm²309 A241 A0.71 V (0.31%)229.3 V1.18 V (0.51%)178.3 W✓ OK (≤3%)
185 mm²353 A275 A0.58 V (0.25%)229.4 V0.95 V (0.41%)144.6 W✓ OK (≤3%)
240 mm²415 A324 A0.45 V (0.19%)229.6 V0.74 V (0.32%)111.5 W✓ OK (≤3%)
300 mm²477 A372 A0.36 V (0.16%)229.6 V0.59 V (0.26%)89.2 W✓ OK (≤3%)
400 mm²570 A445 A0.27 V (0.12%)229.7 V0.44 V (0.19%)66.9 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 250 Ampere ved 10 Meter (230V)

Hvilket kabeltværsnit kræves til 250A ved 10 meter (230V)?

Til 250 Ampere over 10 meter ved 230V anbefales 120 mm² kobberkabel (spændingsfald 0.89V / 0.39%).

Hvor mange kW svarer 250A ved 230V til?

Det svarer til 57.5 kW med en anbefalet sikring på 250A.