Kabeltværsnit for 250 Ampere ved 50 Meter (400V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 250 A over 50 m ved 400V.

Copper Cable (≤3% Drop)120 mm²Drop: 3.86V (0.97%)
Aluminum Cable (≤3% Drop)185 mm²Drop: 4.13V (1.03%)
Voltage at Load396.1 VLine Loss: 1671.9 W
Max Power & Breaker173.21 kW250A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 250A at 50m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A308.88 V (77.22%)91.1 V509.51 V (127.38%)133750.0 WDrop High
2.5 mm²24 A18 A185.33 V (46.33%)214.7 V305.71 V (76.43%)80250.0 WDrop High
4 mm²32 A25 A115.83 V (28.96%)284.2 V191.07 V (47.77%)50156.2 WDrop High
6 mm²41 A32 A77.22 V (19.31%)322.8 V127.38 V (31.84%)33437.5 WDrop High
10 mm²57 A44 A46.33 V (11.58%)353.7 V76.43 V (19.11%)20062.5 WDrop High
16 mm²76 A59 A28.96 V (7.24%)371.0 V47.77 V (11.94%)12539.1 WDrop High
25 mm²101 A78 A18.53 V (4.63%)381.5 V30.57 V (7.64%)8025.0 WDrop High
35 mm²125 A97 A13.24 V (3.31%)386.8 V21.84 V (5.46%)5732.1 WDrop High
50 mm²151 A118 A9.27 V (2.32%)390.7 V15.29 V (3.82%)4012.5 WDrop High
70 mm²192 A150 A6.62 V (1.65%)393.4 V10.92 V (2.73%)2866.1 WDrop High
95 mm²232 A181 A4.88 V (1.22%)395.1 V8.04 V (2.01%)2111.8 WDrop High
120 mm²269 A210 A3.86 V (0.97%)396.1 V6.37 V (1.59%)1671.9 W✓ OK (≤3%)
150 mm²309 A241 A3.09 V (0.77%)396.9 V5.1 V (1.27%)1337.5 W✓ OK (≤3%)
185 mm²353 A275 A2.5 V (0.63%)397.5 V4.13 V (1.03%)1084.5 W✓ OK (≤3%)
240 mm²415 A324 A1.93 V (0.48%)398.1 V3.18 V (0.8%)835.9 W✓ OK (≤3%)
300 mm²477 A372 A1.54 V (0.39%)398.5 V2.55 V (0.64%)668.7 W✓ OK (≤3%)
400 mm²570 A445 A1.16 V (0.29%)398.8 V1.91 V (0.48%)501.6 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 250 Ampere ved 50 Meter (400V)

Hvilket kabeltværsnit kræves til 250A ved 50 meter (400V)?

Til 250 Ampere over 50 meter ved 400V anbefales 120 mm² kobberkabel (spændingsfald 3.86V / 0.97%).

Hvor mange kW svarer 250A ved 400V til?

Det svarer til 173.21 kW med en anbefalet sikring på 250A.