Kabeltværsnit for 35 Ampere ved 175 Meter (230V)
Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 35 A over 175 m ved 230V.
Copper Cable (≤3% Drop)50 mm²Drop: 5.24V (2.28%)
Aluminum Cable (≤3% Drop)70 mm²Drop: 6.18V (2.69%)
Voltage at Load224.8 VLine Loss: 183.5 W
Max Power & Breaker8.05 kW35A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 35A at 175m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 174.77 V (75.99%) | 55.2 V | 288.28 V (125.34%) | 6116.8 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 104.86 V (45.59%) | 125.1 V | 172.97 V (75.2%) | 3670.1 W | Drop High |
| 4 mm² | 32 A | 25 A | 65.54 V (28.49%) | 164.5 V | 108.11 V (47.0%) | 2293.8 W | Drop High |
| 6 mm² | 41 A | 32 A | 43.69 V (19.0%) | 186.3 V | 72.07 V (31.34%) | 1529.2 W | Drop High |
| 10 mm² | 57 A | 44 A | 26.21 V (11.4%) | 203.8 V | 43.24 V (18.8%) | 917.5 W | Drop High |
| 16 mm² | 76 A | 59 A | 16.38 V (7.12%) | 213.6 V | 27.03 V (11.75%) | 573.5 W | Drop High |
| 25 mm² | 101 A | 78 A | 10.49 V (4.56%) | 219.5 V | 17.3 V (7.52%) | 367.0 W | ~ ≤5% |
| 35 mm² | 125 A | 97 A | 7.49 V (3.26%) | 222.5 V | 12.35 V (5.37%) | 262.1 W | ~ ≤5% |
| 50 mm² | 151 A | 118 A | 5.24 V (2.28%) | 224.8 V | 8.65 V (3.76%) | 183.5 W | ✓ OK (≤3%) |
| 70 mm² | 192 A | 150 A | 3.74 V (1.63%) | 226.3 V | 6.18 V (2.69%) | 131.1 W | ✓ OK (≤3%) |
| 95 mm² | 232 A | 181 A | 2.76 V (1.2%) | 227.2 V | 4.55 V (1.98%) | 96.6 W | ✓ OK (≤3%) |
| 120 mm² | 269 A | 210 A | 2.18 V (0.95%) | 227.8 V | 3.6 V (1.57%) | 76.5 W | ✓ OK (≤3%) |
| 150 mm² | 309 A | 241 A | 1.75 V (0.76%) | 228.3 V | 2.88 V (1.25%) | 61.2 W | ✓ OK (≤3%) |
| 185 mm² | 353 A | 275 A | 1.42 V (0.62%) | 228.6 V | 2.34 V (1.02%) | 49.6 W | ✓ OK (≤3%) |
| 240 mm² | 415 A | 324 A | 1.09 V (0.47%) | 228.9 V | 1.8 V (0.78%) | 38.2 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 0.87 V (0.38%) | 229.1 V | 1.44 V (0.63%) | 30.6 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 0.66 V (0.28%) | 229.3 V | 1.08 V (0.47%) | 22.9 W | ✓ OK (≤3%) |
FAQ — Kabeltværsnit for 35 Ampere ved 175 Meter (230V)
Hvilket kabeltværsnit kræves til 35A ved 175 meter (230V)?
Til 35 Ampere over 175 meter ved 230V anbefales 50 mm² kobberkabel (spændingsfald 5.24V / 2.28%).
Hvor mange kW svarer 35A ved 230V til?
Det svarer til 8.05 kW med en anbefalet sikring på 35A.
Related Lengths & Currents (230V)
35A · 5m (230V)35A · 10m (230V)35A · 15m (230V)35A · 20m (230V)35A · 25m (230V)35A · 30m (230V)35A · 35m (230V)35A · 40m (230V)35A · 45m (230V)35A · 50m (230V)35A · 60m (230V)35A · 70m (230V)10A · 175m (230V)16A · 175m (230V)20A · 175m (230V)25A · 175m (230V)32A · 175m (230V)40A · 175m (230V)50A · 175m (230V)63A · 175m (230V)80A · 175m (230V)100A · 175m (230V)125A · 175m (230V)160A · 175m (230V)200A · 175m (230V)