Kabeltværsnit for 35 Ampere ved 400 Meter (230V)
Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 35 A over 400 m ved 230V.
Copper Cable (≤3% Drop)95 mm²Drop: 6.31V (2.74%)
Aluminum Cable (≤3% Drop)150 mm²Drop: 6.59V (2.86%)
Voltage at Load223.7 VLine Loss: 220.8 W
Max Power & Breaker8.05 kW35A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 35A at 400m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 399.47 V (173.68%) | 0.0 V | 658.93 V (286.49%) | 13981.3 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 239.68 V (104.21%) | 0.0 V | 395.36 V (171.9%) | 8388.8 W | Drop High |
| 4 mm² | 32 A | 25 A | 149.8 V (65.13%) | 80.2 V | 247.1 V (107.43%) | 5243.0 W | Drop High |
| 6 mm² | 41 A | 32 A | 99.87 V (43.42%) | 130.1 V | 164.73 V (71.62%) | 3495.3 W | Drop High |
| 10 mm² | 57 A | 44 A | 59.92 V (26.05%) | 170.1 V | 98.84 V (42.97%) | 2097.2 W | Drop High |
| 16 mm² | 76 A | 59 A | 37.45 V (16.28%) | 192.6 V | 61.77 V (26.86%) | 1310.7 W | Drop High |
| 25 mm² | 101 A | 78 A | 23.97 V (10.42%) | 206.0 V | 39.54 V (17.19%) | 838.9 W | Drop High |
| 35 mm² | 125 A | 97 A | 17.12 V (7.44%) | 212.9 V | 28.24 V (12.28%) | 599.2 W | Drop High |
| 50 mm² | 151 A | 118 A | 11.98 V (5.21%) | 218.0 V | 19.77 V (8.59%) | 419.4 W | Drop High |
| 70 mm² | 192 A | 150 A | 8.56 V (3.72%) | 221.4 V | 14.12 V (6.14%) | 299.6 W | ~ ≤5% |
| 95 mm² | 232 A | 181 A | 6.31 V (2.74%) | 223.7 V | 10.4 V (4.52%) | 220.8 W | ✓ OK (≤3%) |
| 120 mm² | 269 A | 210 A | 4.99 V (2.17%) | 225.0 V | 8.24 V (3.58%) | 174.8 W | ✓ OK (≤3%) |
| 150 mm² | 309 A | 241 A | 3.99 V (1.74%) | 226.0 V | 6.59 V (2.86%) | 139.8 W | ✓ OK (≤3%) |
| 185 mm² | 353 A | 275 A | 3.24 V (1.41%) | 226.8 V | 5.34 V (2.32%) | 113.4 W | ✓ OK (≤3%) |
| 240 mm² | 415 A | 324 A | 2.5 V (1.09%) | 227.5 V | 4.12 V (1.79%) | 87.4 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 2.0 V (0.87%) | 228.0 V | 3.29 V (1.43%) | 69.9 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 1.5 V (0.65%) | 228.5 V | 2.47 V (1.07%) | 52.4 W | ✓ OK (≤3%) |
FAQ — Kabeltværsnit for 35 Ampere ved 400 Meter (230V)
Hvilket kabeltværsnit kræves til 35A ved 400 meter (230V)?
Til 35 Ampere over 400 meter ved 230V anbefales 95 mm² kobberkabel (spændingsfald 6.31V / 2.74%).
Hvor mange kW svarer 35A ved 230V til?
Det svarer til 8.05 kW med en anbefalet sikring på 35A.
Related Lengths & Currents (230V)
35A · 5m (230V)35A · 10m (230V)35A · 15m (230V)35A · 20m (230V)35A · 25m (230V)35A · 30m (230V)35A · 35m (230V)35A · 40m (230V)35A · 45m (230V)35A · 50m (230V)35A · 60m (230V)35A · 70m (230V)10A · 400m (230V)16A · 400m (230V)20A · 400m (230V)25A · 400m (230V)32A · 400m (230V)40A · 400m (230V)50A · 400m (230V)63A · 400m (230V)80A · 400m (230V)100A · 400m (230V)125A · 400m (230V)160A · 400m (230V)200A · 400m (230V)