⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabeltværsnit for 400 Ampere ved 40 Meter (230V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 400 A over 40 m ved 230V.

Copper Cable (≤3% Drop)240 mm²Drop: 2.85V (1.24%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 2.82V (1.23%)
Voltage at Load227.1 VLine Loss: 1141.3 W
Max Power & Breaker92.0 kW400A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 400A at 40m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A456.53 V (198.49%)0.0 V753.07 V (327.42%)182613.3 WDrop High
2.5 mm²24 A18 A273.92 V (119.1%)0.0 V451.84 V (196.45%)109568.0 WDrop High
4 mm²32 A25 A171.2 V (74.43%)58.8 V282.4 V (122.78%)68480.0 WDrop High
6 mm²41 A32 A114.13 V (49.62%)115.9 V188.27 V (81.86%)45653.3 WDrop High
10 mm²57 A44 A68.48 V (29.77%)161.5 V112.96 V (49.11%)27392.0 WDrop High
16 mm²76 A59 A42.8 V (18.61%)187.2 V70.6 V (30.7%)17120.0 WDrop High
25 mm²101 A78 A27.39 V (11.91%)202.6 V45.18 V (19.65%)10956.8 WDrop High
35 mm²125 A97 A19.57 V (8.51%)210.4 V32.27 V (14.03%)7826.3 WDrop High
50 mm²151 A118 A13.7 V (5.95%)216.3 V22.59 V (9.82%)5478.4 WDrop High
70 mm²192 A150 A9.78 V (4.25%)220.2 V16.14 V (7.02%)3913.1 WDrop High
95 mm²232 A181 A7.21 V (3.13%)222.8 V11.89 V (5.17%)2883.4 WDrop High
120 mm²269 A210 A5.71 V (2.48%)224.3 V9.41 V (4.09%)2282.7 WDrop High
150 mm²309 A241 A4.57 V (1.98%)225.4 V7.53 V (3.27%)1826.1 WDrop High
185 mm²353 A275 A3.7 V (1.61%)226.3 V6.11 V (2.65%)1480.6 WDrop High
240 mm²415 A324 A2.85 V (1.24%)227.1 V4.71 V (2.05%)1141.3 W✓ OK (≤3%)
300 mm²477 A372 A2.28 V (0.99%)227.7 V3.77 V (1.64%)913.1 W✓ OK (≤3%)
400 mm²570 A445 A1.71 V (0.74%)228.3 V2.82 V (1.23%)684.8 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 400 Ampere ved 40 Meter (230V)

Hvilket kabeltværsnit kræves til 400A ved 40 meter (230V)?

Til 400 Ampere over 40 meter ved 230V anbefales 240 mm² kobberkabel (spændingsfald 2.85V / 1.24%).

Hvor mange kW svarer 400A ved 230V til?

Det svarer til 92.0 kW med en anbefalet sikring på 400A.