⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabeltværsnit for 425 Ampere ved 50 Meter (400V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 425 A over 50 m ved 400V.

Copper Cable (≤3% Drop)300 mm²Drop: 2.63V (0.66%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 3.25V (0.81%)
Voltage at Load397.4 VLine Loss: 1932.7 W
Max Power & Breaker294.45 kW450A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 425A at 50m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A525.1 V (131.28%)0.0 V866.17 V (216.54%)386537.5 WDrop High
2.5 mm²24 A18 A315.06 V (78.77%)84.9 V519.7 V (129.93%)231922.5 WDrop High
4 mm²32 A25 A196.91 V (49.23%)203.1 V324.81 V (81.2%)144951.6 WDrop High
6 mm²41 A32 A131.28 V (32.82%)268.7 V216.54 V (54.14%)96634.4 WDrop High
10 mm²57 A44 A78.77 V (19.69%)321.2 V129.93 V (32.48%)57980.6 WDrop High
16 mm²76 A59 A49.23 V (12.31%)350.8 V81.2 V (20.3%)36237.9 WDrop High
25 mm²101 A78 A31.51 V (7.88%)368.5 V51.97 V (12.99%)23192.2 WDrop High
35 mm²125 A97 A22.5 V (5.63%)377.5 V37.12 V (9.28%)16565.9 WDrop High
50 mm²151 A118 A15.75 V (3.94%)384.2 V25.99 V (6.5%)11596.1 WDrop High
70 mm²192 A150 A11.25 V (2.81%)388.7 V18.56 V (4.64%)8282.9 WDrop High
95 mm²232 A181 A8.29 V (2.07%)391.7 V13.68 V (3.42%)6103.2 WDrop High
120 mm²269 A210 A6.56 V (1.64%)393.4 V10.83 V (2.71%)4831.7 WDrop High
150 mm²309 A241 A5.25 V (1.31%)394.7 V8.66 V (2.17%)3865.4 WDrop High
185 mm²353 A275 A4.26 V (1.06%)395.7 V7.02 V (1.76%)3134.1 WDrop High
240 mm²415 A324 A3.28 V (0.82%)396.7 V5.41 V (1.35%)2415.9 WDrop High
300 mm²477 A372 A2.63 V (0.66%)397.4 V4.33 V (1.08%)1932.7 W✓ OK (≤3%)
400 mm²570 A445 A1.97 V (0.49%)398.0 V3.25 V (0.81%)1449.5 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 425 Ampere ved 50 Meter (400V)

Hvilket kabeltværsnit kræves til 425A ved 50 meter (400V)?

Til 425 Ampere over 50 meter ved 400V anbefales 300 mm² kobberkabel (spændingsfald 2.63V / 0.66%).

Hvor mange kW svarer 425A ved 400V til?

Det svarer til 294.45 kW med en anbefalet sikring på 450A.