Kabeltværsnit for 45 Ampere ved 10 Meter (230V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 45 A over 10 m ved 230V.

Copper Cable (≤3% Drop)10 mm²Drop: 1.93V (0.84%)
Aluminum Cable (≤3% Drop)16 mm²Drop: 1.99V (0.86%)
Voltage at Load228.1 VLine Loss: 86.7 W
Max Power & Breaker10.35 kW45A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 45A at 10m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A12.84 V (5.58%)217.2 V21.18 V (9.21%)577.8 WDrop High
2.5 mm²24 A18 A7.7 V (3.35%)222.3 V12.71 V (5.53%)346.7 WDrop High
4 mm²32 A25 A4.81 V (2.09%)225.2 V7.94 V (3.45%)216.7 WDrop High
6 mm²41 A32 A3.21 V (1.4%)226.8 V5.29 V (2.3%)144.4 WDrop High
10 mm²57 A44 A1.93 V (0.84%)228.1 V3.18 V (1.38%)86.7 W✓ OK (≤3%)
16 mm²76 A59 A1.2 V (0.52%)228.8 V1.99 V (0.86%)54.2 W✓ OK (≤3%)
25 mm²101 A78 A0.77 V (0.33%)229.2 V1.27 V (0.55%)34.7 W✓ OK (≤3%)
35 mm²125 A97 A0.55 V (0.24%)229.4 V0.91 V (0.39%)24.8 W✓ OK (≤3%)
50 mm²151 A118 A0.39 V (0.17%)229.6 V0.64 V (0.28%)17.3 W✓ OK (≤3%)
70 mm²192 A150 A0.28 V (0.12%)229.7 V0.45 V (0.2%)12.4 W✓ OK (≤3%)
95 mm²232 A181 A0.2 V (0.09%)229.8 V0.33 V (0.15%)9.1 W✓ OK (≤3%)
120 mm²269 A210 A0.16 V (0.07%)229.8 V0.26 V (0.12%)7.2 W✓ OK (≤3%)
150 mm²309 A241 A0.13 V (0.06%)229.9 V0.21 V (0.09%)5.8 W✓ OK (≤3%)
185 mm²353 A275 A0.1 V (0.05%)229.9 V0.17 V (0.07%)4.7 W✓ OK (≤3%)
240 mm²415 A324 A0.08 V (0.03%)229.9 V0.13 V (0.06%)3.6 W✓ OK (≤3%)
300 mm²477 A372 A0.06 V (0.03%)229.9 V0.11 V (0.05%)2.9 W✓ OK (≤3%)
400 mm²570 A445 A0.05 V (0.02%)230.0 V0.08 V (0.03%)2.2 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 45 Ampere ved 10 Meter (230V)

Hvilket kabeltværsnit kræves til 45A ved 10 meter (230V)?

Til 45 Ampere over 10 meter ved 230V anbefales 10 mm² kobberkabel (spændingsfald 1.93V / 0.84%).

Hvor mange kW svarer 45A ved 230V til?

Det svarer til 10.35 kW med en anbefalet sikring på 45A.