Kabeltværsnit for 45 Ampere ved 90 Meter (400V)
Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 45 A over 90 m ved 400V.
Copper Cable (≤3% Drop)16 mm²Drop: 9.38V (2.35%)
Aluminum Cable (≤3% Drop)25 mm²Drop: 9.9V (2.48%)
Voltage at Load390.6 VLine Loss: 731.3 W
Max Power & Breaker31.18 kW45A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 45A at 90m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 100.08 V (25.02%) | 299.9 V | 165.08 V (41.27%) | 7800.3 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 60.05 V (15.01%) | 340.0 V | 99.05 V (24.76%) | 4680.2 W | Drop High |
| 4 mm² | 32 A | 25 A | 37.53 V (9.38%) | 362.5 V | 61.91 V (15.48%) | 2925.1 W | Drop High |
| 6 mm² | 41 A | 32 A | 25.02 V (6.25%) | 375.0 V | 41.27 V (10.32%) | 1950.1 W | Drop High |
| 10 mm² | 57 A | 44 A | 15.01 V (3.75%) | 385.0 V | 24.76 V (6.19%) | 1170.0 W | ~ ≤5% |
| 16 mm² | 76 A | 59 A | 9.38 V (2.35%) | 390.6 V | 15.48 V (3.87%) | 731.3 W | ✓ OK (≤3%) |
| 25 mm² | 101 A | 78 A | 6.0 V (1.5%) | 394.0 V | 9.9 V (2.48%) | 468.0 W | ✓ OK (≤3%) |
| 35 mm² | 125 A | 97 A | 4.29 V (1.07%) | 395.7 V | 7.07 V (1.77%) | 334.3 W | ✓ OK (≤3%) |
| 50 mm² | 151 A | 118 A | 3.0 V (0.75%) | 397.0 V | 4.95 V (1.24%) | 234.0 W | ✓ OK (≤3%) |
| 70 mm² | 192 A | 150 A | 2.14 V (0.54%) | 397.9 V | 3.54 V (0.88%) | 167.1 W | ✓ OK (≤3%) |
| 95 mm² | 232 A | 181 A | 1.58 V (0.4%) | 398.4 V | 2.61 V (0.65%) | 123.2 W | ✓ OK (≤3%) |
| 120 mm² | 269 A | 210 A | 1.25 V (0.31%) | 398.7 V | 2.06 V (0.52%) | 97.5 W | ✓ OK (≤3%) |
| 150 mm² | 309 A | 241 A | 1.0 V (0.25%) | 399.0 V | 1.65 V (0.41%) | 78.0 W | ✓ OK (≤3%) |
| 185 mm² | 353 A | 275 A | 0.81 V (0.2%) | 399.2 V | 1.34 V (0.33%) | 63.2 W | ✓ OK (≤3%) |
| 240 mm² | 415 A | 324 A | 0.63 V (0.16%) | 399.4 V | 1.03 V (0.26%) | 48.8 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 0.5 V (0.13%) | 399.5 V | 0.83 V (0.21%) | 39.0 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 0.38 V (0.09%) | 399.6 V | 0.62 V (0.15%) | 29.3 W | ✓ OK (≤3%) |
FAQ — Kabeltværsnit for 45 Ampere ved 90 Meter (400V)
Hvilket kabeltværsnit kræves til 45A ved 90 meter (400V)?
Til 45 Ampere over 90 meter ved 400V anbefales 16 mm² kobberkabel (spændingsfald 9.38V / 2.35%).
Hvor mange kW svarer 45A ved 400V til?
Det svarer til 31.18 kW med en anbefalet sikring på 45A.
Related Lengths & Currents (400V)
45A · 5m (400V)45A · 10m (400V)45A · 15m (400V)45A · 20m (400V)45A · 25m (400V)45A · 30m (400V)45A · 35m (400V)45A · 40m (400V)45A · 45m (400V)45A · 50m (400V)45A · 60m (400V)45A · 70m (400V)10A · 90m (400V)16A · 90m (400V)20A · 90m (400V)25A · 90m (400V)32A · 90m (400V)40A · 90m (400V)50A · 90m (400V)63A · 90m (400V)80A · 90m (400V)100A · 90m (400V)125A · 90m (400V)160A · 90m (400V)200A · 90m (400V)