⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabeltværsnit for 450 Ampere ved 50 Meter (400V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 450 A over 50 m ved 400V.

Copper Cable (≤3% Drop)300 mm²Drop: 2.78V (0.69%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 3.44V (0.86%)
Voltage at Load397.2 VLine Loss: 2166.8 W
Max Power & Breaker311.77 kW450A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 450A at 50m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A555.99 V (139.0%)0.0 V917.12 V (229.28%)433350.0 WDrop High
2.5 mm²24 A18 A333.59 V (83.4%)66.4 V550.27 V (137.57%)260010.0 WDrop High
4 mm²32 A25 A208.5 V (52.12%)191.5 V343.92 V (85.98%)162506.2 WDrop High
6 mm²41 A32 A139.0 V (34.75%)261.0 V229.28 V (57.32%)108337.5 WDrop High
10 mm²57 A44 A83.4 V (20.85%)316.6 V137.57 V (34.39%)65002.5 WDrop High
16 mm²76 A59 A52.12 V (13.03%)347.9 V85.98 V (21.5%)40626.6 WDrop High
25 mm²101 A78 A33.36 V (8.34%)366.6 V55.03 V (13.76%)26001.0 WDrop High
35 mm²125 A97 A23.83 V (5.96%)376.2 V39.31 V (9.83%)18572.1 WDrop High
50 mm²151 A118 A16.68 V (4.17%)383.3 V27.51 V (6.88%)13000.5 WDrop High
70 mm²192 A150 A11.91 V (2.98%)388.1 V19.65 V (4.91%)9286.1 WDrop High
95 mm²232 A181 A8.78 V (2.19%)391.2 V14.48 V (3.62%)6842.4 WDrop High
120 mm²269 A210 A6.95 V (1.74%)393.1 V11.46 V (2.87%)5416.9 WDrop High
150 mm²309 A241 A5.56 V (1.39%)394.4 V9.17 V (2.29%)4333.5 WDrop High
185 mm²353 A275 A4.51 V (1.13%)395.5 V7.44 V (1.86%)3513.6 WDrop High
240 mm²415 A324 A3.47 V (0.87%)396.5 V5.73 V (1.43%)2708.4 WDrop High
300 mm²477 A372 A2.78 V (0.69%)397.2 V4.59 V (1.15%)2166.8 W✓ OK (≤3%)
400 mm²570 A445 A2.08 V (0.52%)397.9 V3.44 V (0.86%)1625.1 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 450 Ampere ved 50 Meter (400V)

Hvilket kabeltværsnit kræves til 450A ved 50 meter (400V)?

Til 450 Ampere over 50 meter ved 400V anbefales 300 mm² kobberkabel (spændingsfald 2.78V / 0.69%).

Hvor mange kW svarer 450A ved 400V til?

Det svarer til 311.77 kW med en anbefalet sikring på 450A.