Kabeltværsnit for 475 Ampere ved 5 Meter (230V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 475 A over 5 m ved 230V.

Copper Cable (≤3% Drop)300 mm²Drop: 0.34V (0.15%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 0.42V (0.18%)
Voltage at Load229.7 VLine Loss: 160.9 W
Max Power & Breaker109.25 kW500A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 475A at 5m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A67.77 V (29.46%)162.2 V111.78 V (48.6%)32189.2 WDrop High
2.5 mm²24 A18 A40.66 V (17.68%)189.3 V67.07 V (29.16%)19313.5 WDrop High
4 mm²32 A25 A25.41 V (11.05%)204.6 V41.92 V (18.23%)12070.9 WDrop High
6 mm²41 A32 A16.94 V (7.37%)213.1 V27.95 V (12.15%)8047.3 WDrop High
10 mm²57 A44 A10.16 V (4.42%)219.8 V16.77 V (7.29%)4828.4 WDrop High
16 mm²76 A59 A6.35 V (2.76%)223.6 V10.48 V (4.56%)3017.7 WDrop High
25 mm²101 A78 A4.07 V (1.77%)225.9 V6.71 V (2.92%)1931.3 WDrop High
35 mm²125 A97 A2.9 V (1.26%)227.1 V4.79 V (2.08%)1379.5 WDrop High
50 mm²151 A118 A2.03 V (0.88%)228.0 V3.35 V (1.46%)965.7 WDrop High
70 mm²192 A150 A1.45 V (0.63%)228.5 V2.4 V (1.04%)689.8 WDrop High
95 mm²232 A181 A1.07 V (0.47%)228.9 V1.76 V (0.77%)508.2 WDrop High
120 mm²269 A210 A0.85 V (0.37%)229.2 V1.4 V (0.61%)402.4 WDrop High
150 mm²309 A241 A0.68 V (0.29%)229.3 V1.12 V (0.49%)321.9 WDrop High
185 mm²353 A275 A0.55 V (0.24%)229.5 V0.91 V (0.39%)261.0 WDrop High
240 mm²415 A324 A0.42 V (0.18%)229.6 V0.7 V (0.3%)201.2 WDrop High
300 mm²477 A372 A0.34 V (0.15%)229.7 V0.56 V (0.24%)160.9 W✓ OK (≤3%)
400 mm²570 A445 A0.25 V (0.11%)229.7 V0.42 V (0.18%)120.7 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 475 Ampere ved 5 Meter (230V)

Hvilket kabeltværsnit kræves til 475A ved 5 meter (230V)?

Til 475 Ampere over 5 meter ved 230V anbefales 300 mm² kobberkabel (spændingsfald 0.34V / 0.15%).

Hvor mange kW svarer 475A ved 230V til?

Det svarer til 109.25 kW med en anbefalet sikring på 500A.