Kabeltværsnit for 475 Ampere ved 20 Meter (230V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 475 A over 20 m ved 230V.

Copper Cable (≤3% Drop)300 mm²Drop: 1.36V (0.59%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 1.68V (0.73%)
Voltage at Load228.6 VLine Loss: 643.8 W
Max Power & Breaker109.25 kW500A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 475A at 20m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A271.07 V (117.86%)0.0 V447.13 V (194.41%)128756.7 WDrop High
2.5 mm²24 A18 A162.64 V (70.71%)67.4 V268.28 V (116.64%)77254.0 WDrop High
4 mm²32 A25 A101.65 V (44.2%)128.4 V167.67 V (72.9%)48283.8 WDrop High
6 mm²41 A32 A67.77 V (29.46%)162.2 V111.78 V (48.6%)32189.2 WDrop High
10 mm²57 A44 A40.66 V (17.68%)189.3 V67.07 V (29.16%)19313.5 WDrop High
16 mm²76 A59 A25.41 V (11.05%)204.6 V41.92 V (18.23%)12070.9 WDrop High
25 mm²101 A78 A16.26 V (7.07%)213.7 V26.83 V (11.66%)7725.4 WDrop High
35 mm²125 A97 A11.62 V (5.05%)218.4 V19.16 V (8.33%)5518.1 WDrop High
50 mm²151 A118 A8.13 V (3.54%)221.9 V13.41 V (5.83%)3862.7 WDrop High
70 mm²192 A150 A5.81 V (2.53%)224.2 V9.58 V (4.17%)2759.1 WDrop High
95 mm²232 A181 A4.28 V (1.86%)225.7 V7.06 V (3.07%)2033.0 WDrop High
120 mm²269 A210 A3.39 V (1.47%)226.6 V5.59 V (2.43%)1609.5 WDrop High
150 mm²309 A241 A2.71 V (1.18%)227.3 V4.47 V (1.94%)1287.6 WDrop High
185 mm²353 A275 A2.2 V (0.96%)227.8 V3.63 V (1.58%)1044.0 WDrop High
240 mm²415 A324 A1.69 V (0.74%)228.3 V2.79 V (1.22%)804.7 WDrop High
300 mm²477 A372 A1.36 V (0.59%)228.6 V2.24 V (0.97%)643.8 W✓ OK (≤3%)
400 mm²570 A445 A1.02 V (0.44%)229.0 V1.68 V (0.73%)482.8 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 475 Ampere ved 20 Meter (230V)

Hvilket kabeltværsnit kræves til 475A ved 20 meter (230V)?

Til 475 Ampere over 20 meter ved 230V anbefales 300 mm² kobberkabel (spændingsfald 1.36V / 0.59%).

Hvor mange kW svarer 475A ved 230V til?

Det svarer til 109.25 kW med en anbefalet sikring på 500A.