Kabeltværsnit for 475 Ampere ved 10 Meter (230V)
Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 475 A over 10 m ved 230V.
Copper Cable (≤3% Drop)300 mm²Drop: 0.68V (0.29%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 0.84V (0.36%)
Voltage at Load229.3 VLine Loss: 321.9 W
Max Power & Breaker109.25 kW500A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 475A at 10m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 135.53 V (58.93%) | 94.5 V | 223.57 V (97.2%) | 64378.3 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 81.32 V (35.36%) | 148.7 V | 134.14 V (58.32%) | 38627.0 W | Drop High |
| 4 mm² | 32 A | 25 A | 50.82 V (22.1%) | 179.2 V | 83.84 V (36.45%) | 24141.9 W | Drop High |
| 6 mm² | 41 A | 32 A | 33.88 V (14.73%) | 196.1 V | 55.89 V (24.3%) | 16094.6 W | Drop High |
| 10 mm² | 57 A | 44 A | 20.33 V (8.84%) | 209.7 V | 33.53 V (14.58%) | 9656.8 W | Drop High |
| 16 mm² | 76 A | 59 A | 12.71 V (5.52%) | 217.3 V | 20.96 V (9.11%) | 6035.5 W | Drop High |
| 25 mm² | 101 A | 78 A | 8.13 V (3.54%) | 221.9 V | 13.41 V (5.83%) | 3862.7 W | Drop High |
| 35 mm² | 125 A | 97 A | 5.81 V (2.53%) | 224.2 V | 9.58 V (4.17%) | 2759.1 W | Drop High |
| 50 mm² | 151 A | 118 A | 4.07 V (1.77%) | 225.9 V | 6.71 V (2.92%) | 1931.3 W | Drop High |
| 70 mm² | 192 A | 150 A | 2.9 V (1.26%) | 227.1 V | 4.79 V (2.08%) | 1379.5 W | Drop High |
| 95 mm² | 232 A | 181 A | 2.14 V (0.93%) | 227.9 V | 3.53 V (1.53%) | 1016.5 W | Drop High |
| 120 mm² | 269 A | 210 A | 1.69 V (0.74%) | 228.3 V | 2.79 V (1.22%) | 804.7 W | Drop High |
| 150 mm² | 309 A | 241 A | 1.36 V (0.59%) | 228.6 V | 2.24 V (0.97%) | 643.8 W | Drop High |
| 185 mm² | 353 A | 275 A | 1.1 V (0.48%) | 228.9 V | 1.81 V (0.79%) | 522.0 W | Drop High |
| 240 mm² | 415 A | 324 A | 0.85 V (0.37%) | 229.2 V | 1.4 V (0.61%) | 402.4 W | Drop High |
| 300 mm² | 477 A | 372 A | 0.68 V (0.29%) | 229.3 V | 1.12 V (0.49%) | 321.9 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 0.51 V (0.22%) | 229.5 V | 0.84 V (0.36%) | 241.4 W | ✓ OK (≤3%) |
FAQ — Kabeltværsnit for 475 Ampere ved 10 Meter (230V)
Hvilket kabeltværsnit kræves til 475A ved 10 meter (230V)?
Til 475 Ampere over 10 meter ved 230V anbefales 300 mm² kobberkabel (spændingsfald 0.68V / 0.29%).
Hvor mange kW svarer 475A ved 230V til?
Det svarer til 109.25 kW med en anbefalet sikring på 500A.
Related Lengths & Currents (230V)
475A · 5m (230V)475A · 15m (230V)475A · 20m (230V)475A · 25m (230V)475A · 30m (230V)475A · 35m (230V)475A · 40m (230V)475A · 45m (230V)475A · 50m (230V)475A · 60m (230V)475A · 70m (230V)10A · 10m (230V)16A · 10m (230V)20A · 10m (230V)25A · 10m (230V)32A · 10m (230V)40A · 10m (230V)50A · 10m (230V)63A · 10m (230V)80A · 10m (230V)100A · 10m (230V)125A · 10m (230V)160A · 10m (230V)200A · 10m (230V)