Kabeltværsnit for 475 Ampere ved 15 Meter (230V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 475 A over 15 m ved 230V.

Copper Cable (≤3% Drop)300 mm²Drop: 1.02V (0.44%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 1.26V (0.55%)
Voltage at Load229.0 VLine Loss: 482.8 W
Max Power & Breaker109.25 kW500A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 475A at 15m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A203.3 V (88.39%)26.7 V335.35 V (145.8%)96567.5 WDrop High
2.5 mm²24 A18 A121.98 V (53.03%)108.0 V201.21 V (87.48%)57940.5 WDrop High
4 mm²32 A25 A76.24 V (33.15%)153.8 V125.76 V (54.68%)36212.8 WDrop High
6 mm²41 A32 A50.82 V (22.1%)179.2 V83.84 V (36.45%)24141.9 WDrop High
10 mm²57 A44 A30.5 V (13.26%)199.5 V50.3 V (21.87%)14485.1 WDrop High
16 mm²76 A59 A19.06 V (8.29%)210.9 V31.44 V (13.67%)9053.2 WDrop High
25 mm²101 A78 A12.2 V (5.3%)217.8 V20.12 V (8.75%)5794.1 WDrop High
35 mm²125 A97 A8.71 V (3.79%)221.3 V14.37 V (6.25%)4138.6 WDrop High
50 mm²151 A118 A6.1 V (2.65%)223.9 V10.06 V (4.37%)2897.0 WDrop High
70 mm²192 A150 A4.36 V (1.89%)225.6 V7.19 V (3.12%)2069.3 WDrop High
95 mm²232 A181 A3.21 V (1.4%)226.8 V5.29 V (2.3%)1524.8 WDrop High
120 mm²269 A210 A2.54 V (1.1%)227.5 V4.19 V (1.82%)1207.1 WDrop High
150 mm²309 A241 A2.03 V (0.88%)228.0 V3.35 V (1.46%)965.7 WDrop High
185 mm²353 A275 A1.65 V (0.72%)228.4 V2.72 V (1.18%)783.0 WDrop High
240 mm²415 A324 A1.27 V (0.55%)228.7 V2.1 V (0.91%)603.5 WDrop High
300 mm²477 A372 A1.02 V (0.44%)229.0 V1.68 V (0.73%)482.8 W✓ OK (≤3%)
400 mm²570 A445 A0.76 V (0.33%)229.2 V1.26 V (0.55%)362.1 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 475 Ampere ved 15 Meter (230V)

Hvilket kabeltværsnit kræves til 475A ved 15 meter (230V)?

Til 475 Ampere over 15 meter ved 230V anbefales 300 mm² kobberkabel (spændingsfald 1.02V / 0.44%).

Hvor mange kW svarer 475A ved 230V til?

Det svarer til 109.25 kW med en anbefalet sikring på 500A.