Kabeltværsnit for 5 Ampere ved 175 Meter (400V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 5 A over 175 m ved 400V.

Copper Cable (≤3% Drop)4 mm²Drop: 8.11V (2.03%)
Aluminum Cable (≤3% Drop)6 mm²Drop: 8.92V (2.23%)
Voltage at Load391.9 VLine Loss: 70.2 W
Max Power & Breaker3.46 kW6A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 5A at 175m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A21.62 V (5.41%)378.4 V35.67 V (8.92%)187.2 WDrop High
2.5 mm²24 A18 A12.97 V (3.24%)387.0 V21.4 V (5.35%)112.3 W~ ≤5%
4 mm²32 A25 A8.11 V (2.03%)391.9 V13.37 V (3.34%)70.2 W✓ OK (≤3%)
6 mm²41 A32 A5.41 V (1.35%)394.6 V8.92 V (2.23%)46.8 W✓ OK (≤3%)
10 mm²57 A44 A3.24 V (0.81%)396.8 V5.35 V (1.34%)28.1 W✓ OK (≤3%)
16 mm²76 A59 A2.03 V (0.51%)398.0 V3.34 V (0.84%)17.6 W✓ OK (≤3%)
25 mm²101 A78 A1.3 V (0.32%)398.7 V2.14 V (0.53%)11.2 W✓ OK (≤3%)
35 mm²125 A97 A0.93 V (0.23%)399.1 V1.53 V (0.38%)8.0 W✓ OK (≤3%)
50 mm²151 A118 A0.65 V (0.16%)399.4 V1.07 V (0.27%)5.6 W✓ OK (≤3%)
70 mm²192 A150 A0.46 V (0.12%)399.5 V0.76 V (0.19%)4.0 W✓ OK (≤3%)
95 mm²232 A181 A0.34 V (0.09%)399.7 V0.56 V (0.14%)3.0 W✓ OK (≤3%)
120 mm²269 A210 A0.27 V (0.07%)399.7 V0.45 V (0.11%)2.3 W✓ OK (≤3%)
150 mm²309 A241 A0.22 V (0.05%)399.8 V0.36 V (0.09%)1.9 W✓ OK (≤3%)
185 mm²353 A275 A0.18 V (0.04%)399.8 V0.29 V (0.07%)1.5 W✓ OK (≤3%)
240 mm²415 A324 A0.14 V (0.03%)399.9 V0.22 V (0.06%)1.2 W✓ OK (≤3%)
300 mm²477 A372 A0.11 V (0.03%)399.9 V0.18 V (0.04%)0.9 W✓ OK (≤3%)
400 mm²570 A445 A0.08 V (0.02%)399.9 V0.13 V (0.03%)0.7 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 5 Ampere ved 175 Meter (400V)

Hvilket kabeltværsnit kræves til 5A ved 175 meter (400V)?

Til 5 Ampere over 175 meter ved 400V anbefales 4 mm² kobberkabel (spændingsfald 8.11V / 2.03%).

Hvor mange kW svarer 5A ved 400V til?

Det svarer til 3.46 kW med en anbefalet sikring på 6A.