Kabeltværsnit for 500 Ampere ved 175 Meter (400V)
Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 500 A over 175 m ved 400V.
Copper Cable (≤3% Drop)400 mm²Drop: 8.11V (2.03%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 13.37V (3.34%)
Voltage at Load391.9 VLine Loss: 7021.9 W
Max Power & Breaker346.41 kW500A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 500A at 175m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 2162.18 V (540.54%) | 0.0 V | 3566.58 V (891.65%) | 1872500.0 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 1297.31 V (324.33%) | 0.0 V | 2139.95 V (534.99%) | 1123500.0 W | Drop High |
| 4 mm² | 32 A | 25 A | 810.82 V (202.7%) | 0.0 V | 1337.47 V (334.37%) | 702187.5 W | Drop High |
| 6 mm² | 41 A | 32 A | 540.54 V (135.14%) | 0.0 V | 891.65 V (222.91%) | 468125.0 W | Drop High |
| 10 mm² | 57 A | 44 A | 324.33 V (81.08%) | 75.7 V | 534.99 V (133.75%) | 280875.0 W | Drop High |
| 16 mm² | 76 A | 59 A | 202.7 V (50.68%) | 197.3 V | 334.37 V (83.59%) | 175546.9 W | Drop High |
| 25 mm² | 101 A | 78 A | 129.73 V (32.43%) | 270.3 V | 213.99 V (53.5%) | 112350.0 W | Drop High |
| 35 mm² | 125 A | 97 A | 92.66 V (23.17%) | 307.3 V | 152.85 V (38.21%) | 80250.0 W | Drop High |
| 50 mm² | 151 A | 118 A | 64.87 V (16.22%) | 335.1 V | 107.0 V (26.75%) | 56175.0 W | Drop High |
| 70 mm² | 192 A | 150 A | 46.33 V (11.58%) | 353.7 V | 76.43 V (19.11%) | 40125.0 W | Drop High |
| 95 mm² | 232 A | 181 A | 34.14 V (8.53%) | 365.9 V | 56.31 V (14.08%) | 29565.8 W | Drop High |
| 120 mm² | 269 A | 210 A | 27.03 V (6.76%) | 373.0 V | 44.58 V (11.15%) | 23406.2 W | Drop High |
| 150 mm² | 309 A | 241 A | 21.62 V (5.41%) | 378.4 V | 35.67 V (8.92%) | 18725.0 W | Drop High |
| 185 mm² | 353 A | 275 A | 17.53 V (4.38%) | 382.5 V | 28.92 V (7.23%) | 15182.4 W | Drop High |
| 240 mm² | 415 A | 324 A | 13.51 V (3.38%) | 386.5 V | 22.29 V (5.57%) | 11703.1 W | Drop High |
| 300 mm² | 477 A | 372 A | 10.81 V (2.7%) | 389.2 V | 17.83 V (4.46%) | 9362.5 W | Drop High |
| 400 mm² | 570 A | 445 A | 8.11 V (2.03%) | 391.9 V | 13.37 V (3.34%) | 7021.9 W | ✓ OK (≤3%) |
FAQ — Kabeltværsnit for 500 Ampere ved 175 Meter (400V)
Hvilket kabeltværsnit kræves til 500A ved 175 meter (400V)?
Til 500 Ampere over 175 meter ved 400V anbefales 400 mm² kobberkabel (spændingsfald 8.11V / 2.03%).
Hvor mange kW svarer 500A ved 400V til?
Det svarer til 346.41 kW med en anbefalet sikring på 500A.
Related Lengths & Currents (400V)
500A · 5m (400V)500A · 10m (400V)500A · 15m (400V)500A · 20m (400V)500A · 25m (400V)500A · 30m (400V)500A · 35m (400V)500A · 40m (400V)500A · 45m (400V)500A · 50m (400V)500A · 60m (400V)500A · 70m (400V)10A · 175m (400V)16A · 175m (400V)20A · 175m (400V)25A · 175m (400V)32A · 175m (400V)40A · 175m (400V)50A · 175m (400V)63A · 175m (400V)80A · 175m (400V)100A · 175m (400V)125A · 175m (400V)160A · 175m (400V)200A · 175m (400V)