Kabeltværsnit for 500 Ampere ved 50 Meter (400V)
Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 500 A over 50 m ved 400V.
Copper Cable (≤3% Drop)400 mm²Drop: 2.32V (0.58%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 3.82V (0.96%)
Voltage at Load397.7 VLine Loss: 2006.2 W
Max Power & Breaker346.41 kW500A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 500A at 50m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 617.76 V (154.44%) | 0.0 V | 1019.02 V (254.76%) | 535000.0 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 370.66 V (92.66%) | 29.3 V | 611.41 V (152.85%) | 321000.0 W | Drop High |
| 4 mm² | 32 A | 25 A | 231.66 V (57.92%) | 168.3 V | 382.13 V (95.53%) | 200625.0 W | Drop High |
| 6 mm² | 41 A | 32 A | 154.44 V (38.61%) | 245.6 V | 254.76 V (63.69%) | 133750.0 W | Drop High |
| 10 mm² | 57 A | 44 A | 92.66 V (23.17%) | 307.3 V | 152.85 V (38.21%) | 80250.0 W | Drop High |
| 16 mm² | 76 A | 59 A | 57.92 V (14.48%) | 342.1 V | 95.53 V (23.88%) | 50156.2 W | Drop High |
| 25 mm² | 101 A | 78 A | 37.07 V (9.27%) | 362.9 V | 61.14 V (15.29%) | 32100.0 W | Drop High |
| 35 mm² | 125 A | 97 A | 26.48 V (6.62%) | 373.5 V | 43.67 V (10.92%) | 22928.6 W | Drop High |
| 50 mm² | 151 A | 118 A | 18.53 V (4.63%) | 381.5 V | 30.57 V (7.64%) | 16050.0 W | Drop High |
| 70 mm² | 192 A | 150 A | 13.24 V (3.31%) | 386.8 V | 21.84 V (5.46%) | 11464.3 W | Drop High |
| 95 mm² | 232 A | 181 A | 9.75 V (2.44%) | 390.2 V | 16.09 V (4.02%) | 8447.4 W | Drop High |
| 120 mm² | 269 A | 210 A | 7.72 V (1.93%) | 392.3 V | 12.74 V (3.18%) | 6687.5 W | Drop High |
| 150 mm² | 309 A | 241 A | 6.18 V (1.54%) | 393.8 V | 10.19 V (2.55%) | 5350.0 W | Drop High |
| 185 mm² | 353 A | 275 A | 5.01 V (1.25%) | 395.0 V | 8.26 V (2.07%) | 4337.8 W | Drop High |
| 240 mm² | 415 A | 324 A | 3.86 V (0.97%) | 396.1 V | 6.37 V (1.59%) | 3343.7 W | Drop High |
| 300 mm² | 477 A | 372 A | 3.09 V (0.77%) | 396.9 V | 5.1 V (1.27%) | 2675.0 W | Drop High |
| 400 mm² | 570 A | 445 A | 2.32 V (0.58%) | 397.7 V | 3.82 V (0.96%) | 2006.2 W | ✓ OK (≤3%) |
FAQ — Kabeltværsnit for 500 Ampere ved 50 Meter (400V)
Hvilket kabeltværsnit kræves til 500A ved 50 meter (400V)?
Til 500 Ampere over 50 meter ved 400V anbefales 400 mm² kobberkabel (spændingsfald 2.32V / 0.58%).
Hvor mange kW svarer 500A ved 400V til?
Det svarer til 346.41 kW med en anbefalet sikring på 500A.
Related Lengths & Currents (400V)
500A · 5m (400V)500A · 10m (400V)500A · 15m (400V)500A · 20m (400V)500A · 25m (400V)500A · 30m (400V)500A · 35m (400V)500A · 40m (400V)500A · 45m (400V)500A · 60m (400V)500A · 70m (400V)10A · 50m (400V)16A · 50m (400V)20A · 50m (400V)25A · 50m (400V)32A · 50m (400V)40A · 50m (400V)50A · 50m (400V)63A · 50m (400V)80A · 50m (400V)100A · 50m (400V)125A · 50m (400V)160A · 50m (400V)200A · 50m (400V)