⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabeltværsnit for 550 Ampere ved 90 Meter (230V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 550 A over 90 m ved 230V.

Copper Cable (≤3% Drop)400 mm²Drop: 5.3V (2.3%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 8.74V (3.8%)
Voltage at Load224.7 VLine Loss: 2913.1 W
Max Power & Breaker126.5 kW600A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 550A at 90m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1412.4 V (614.09%)0.0 V2329.8 V (1012.96%)776820.0 WDrop High
2.5 mm²24 A18 A847.44 V (368.45%)0.0 V1397.88 V (607.77%)466092.0 WDrop High
4 mm²32 A25 A529.65 V (230.28%)0.0 V873.67 V (379.86%)291307.5 WDrop High
6 mm²41 A32 A353.1 V (153.52%)0.0 V582.45 V (253.24%)194205.0 WDrop High
10 mm²57 A44 A211.86 V (92.11%)18.1 V349.47 V (151.94%)116523.0 WDrop High
16 mm²76 A59 A132.41 V (57.57%)97.6 V218.42 V (94.96%)72826.9 WDrop High
25 mm²101 A78 A84.74 V (36.85%)145.3 V139.79 V (60.78%)46609.2 WDrop High
35 mm²125 A97 A60.53 V (26.32%)169.5 V99.85 V (43.41%)33292.3 WDrop High
50 mm²151 A118 A42.37 V (18.42%)187.6 V69.89 V (30.39%)23304.6 WDrop High
70 mm²192 A150 A30.27 V (13.16%)199.7 V49.92 V (21.71%)16646.1 WDrop High
95 mm²232 A181 A22.3 V (9.7%)207.7 V36.79 V (15.99%)12265.6 WDrop High
120 mm²269 A210 A17.65 V (7.68%)212.3 V29.12 V (12.66%)9710.2 WDrop High
150 mm²309 A241 A14.12 V (6.14%)215.9 V23.3 V (10.13%)7768.2 WDrop High
185 mm²353 A275 A11.45 V (4.98%)218.5 V18.89 V (8.21%)6298.5 WDrop High
240 mm²415 A324 A8.83 V (3.84%)221.2 V14.56 V (6.33%)4855.1 WDrop High
300 mm²477 A372 A7.06 V (3.07%)222.9 V11.65 V (5.06%)3884.1 WDrop High
400 mm²570 A445 A5.3 V (2.3%)224.7 V8.74 V (3.8%)2913.1 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 550 Ampere ved 90 Meter (230V)

Hvilket kabeltværsnit kræves til 550A ved 90 meter (230V)?

Til 550 Ampere over 90 meter ved 230V anbefales 400 mm² kobberkabel (spændingsfald 5.3V / 2.3%).

Hvor mange kW svarer 550A ved 230V til?

Det svarer til 126.5 kW med en anbefalet sikring på 600A.