Kabelquerschnitt für 100 Ampere bei 300 Meter (400V)

Berechnung des erforderlichen Leiterquerschnitts (mm²) und des Spannungsfalls nach DIN VDE 0100-520 / IEC 60364 für 100 A über 300 m einfache Leitungslänge bei 400V.

Copper Cable (≤3% Drop)95 mm²Drop: 11.71V (2.93%)
Aluminum Cable (≤3% Drop)185 mm²Drop: 9.91V (2.48%)
Voltage at Load388.3 VLine Loss: 2027.4 W
Max Power & Breaker69.28 kW100A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 100A at 300m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A741.32 V (185.33%)0.0 V1222.83 V (305.71%)128400.0 WDrop High
2.5 mm²24 A18 A444.79 V (111.2%)0.0 V733.7 V (183.42%)77040.0 WDrop High
4 mm²32 A25 A277.99 V (69.5%)122.0 V458.56 V (114.64%)48150.0 WDrop High
6 mm²41 A32 A185.33 V (46.33%)214.7 V305.71 V (76.43%)32100.0 WDrop High
10 mm²57 A44 A111.2 V (27.8%)288.8 V183.42 V (45.86%)19260.0 WDrop High
16 mm²76 A59 A69.5 V (17.37%)330.5 V114.64 V (28.66%)12037.5 WDrop High
25 mm²101 A78 A44.48 V (11.12%)355.5 V73.37 V (18.34%)7704.0 WDrop High
35 mm²125 A97 A31.77 V (7.94%)368.2 V52.41 V (13.1%)5502.9 WDrop High
50 mm²151 A118 A22.24 V (5.56%)377.8 V36.68 V (9.17%)3852.0 WDrop High
70 mm²192 A150 A15.89 V (3.97%)384.1 V26.2 V (6.55%)2751.4 W~ ≤5%
95 mm²232 A181 A11.71 V (2.93%)388.3 V19.31 V (4.83%)2027.4 W✓ OK (≤3%)
120 mm²269 A210 A9.27 V (2.32%)390.7 V15.29 V (3.82%)1605.0 W✓ OK (≤3%)
150 mm²309 A241 A7.41 V (1.85%)392.6 V12.23 V (3.06%)1284.0 W✓ OK (≤3%)
185 mm²353 A275 A6.01 V (1.5%)394.0 V9.91 V (2.48%)1041.1 W✓ OK (≤3%)
240 mm²415 A324 A4.63 V (1.16%)395.4 V7.64 V (1.91%)802.5 W✓ OK (≤3%)
300 mm²477 A372 A3.71 V (0.93%)396.3 V6.11 V (1.53%)642.0 W✓ OK (≤3%)
400 mm²570 A445 A2.78 V (0.69%)397.2 V4.59 V (1.15%)481.5 W✓ OK (≤3%)

FAQ — Kabelquerschnitt für 100 Ampere bei 300 Meter (400V)

Welcher Kabelquerschnitt wird für 100A bei 300m (400V) benötigt?

Für 100 Ampere über 300 Meter bei 400V wird ein Kupferkabel von 95 mm² empfohlen, um den Spannungsfall unter 3% (11.71V bzw. 2.93%) zu halten.

Wie hoch ist die maximale Leistung bei 100A und 400V?

Die übertragbare Leistung beträgt 69.28 kW bei einer empfohlenen Absicherung von 100A.