⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabelquerschnitt für 25 Ampere bei 300 Meter (400V)

Berechnung des erforderlichen Leiterquerschnitts (mm²) und des Spannungsfalls nach DIN VDE 0100-520 / IEC 60364 für 25 A über 300 m einfache Leitungslänge bei 400V.

Copper Cable (≤3% Drop)25 mm²Drop: 11.12V (2.78%)
Aluminum Cable (≤3% Drop)50 mm²Drop: 9.17V (2.29%)
Voltage at Load388.9 VLine Loss: 481.5 W
Max Power & Breaker17.32 kW25A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 25A at 300m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A185.33 V (46.33%)214.7 V305.71 V (76.43%)8025.0 WDrop High
2.5 mm²24 A18 A111.2 V (27.8%)288.8 V183.42 V (45.86%)4815.0 WDrop High
4 mm²32 A25 A69.5 V (17.37%)330.5 V114.64 V (28.66%)3009.4 WDrop High
6 mm²41 A32 A46.33 V (11.58%)353.7 V76.43 V (19.11%)2006.3 WDrop High
10 mm²57 A44 A27.8 V (6.95%)372.2 V45.86 V (11.46%)1203.8 WDrop High
16 mm²76 A59 A17.37 V (4.34%)382.6 V28.66 V (7.17%)752.3 W~ ≤5%
25 mm²101 A78 A11.12 V (2.78%)388.9 V18.34 V (4.59%)481.5 W✓ OK (≤3%)
35 mm²125 A97 A7.94 V (1.99%)392.1 V13.1 V (3.28%)343.9 W✓ OK (≤3%)
50 mm²151 A118 A5.56 V (1.39%)394.4 V9.17 V (2.29%)240.7 W✓ OK (≤3%)
70 mm²192 A150 A3.97 V (0.99%)396.0 V6.55 V (1.64%)172.0 W✓ OK (≤3%)
95 mm²232 A181 A2.93 V (0.73%)397.1 V4.83 V (1.21%)126.7 W✓ OK (≤3%)
120 mm²269 A210 A2.32 V (0.58%)397.7 V3.82 V (0.96%)100.3 W✓ OK (≤3%)
150 mm²309 A241 A1.85 V (0.46%)398.1 V3.06 V (0.76%)80.2 W✓ OK (≤3%)
185 mm²353 A275 A1.5 V (0.38%)398.5 V2.48 V (0.62%)65.1 W✓ OK (≤3%)
240 mm²415 A324 A1.16 V (0.29%)398.8 V1.91 V (0.48%)50.2 W✓ OK (≤3%)
300 mm²477 A372 A0.93 V (0.23%)399.1 V1.53 V (0.38%)40.1 W✓ OK (≤3%)
400 mm²570 A445 A0.69 V (0.17%)399.3 V1.15 V (0.29%)30.1 W✓ OK (≤3%)

FAQ — Kabelquerschnitt für 25 Ampere bei 300 Meter (400V)

Welcher Kabelquerschnitt wird für 25A bei 300m (400V) benötigt?

Für 25 Ampere über 300 Meter bei 400V wird ein Kupferkabel von 25 mm² empfohlen, um den Spannungsfall unter 3% (11.12V bzw. 2.78%) zu halten.

Wie hoch ist die maximale Leistung bei 25A und 400V?

Die übertragbare Leistung beträgt 17.32 kW bei einer empfohlenen Absicherung von 25A.