Kabelquerschnitt für 160 Ampere bei 300 Meter (400V)

Berechnung des erforderlichen Leiterquerschnitts (mm²) und des Spannungsfalls nach DIN VDE 0100-520 / IEC 60364 für 160 A über 300 m einfache Leitungslänge bei 400V.

Copper Cable (≤3% Drop)150 mm²Drop: 11.86V (2.97%)
Aluminum Cable (≤3% Drop)300 mm²Drop: 9.78V (2.45%)
Voltage at Load388.1 VLine Loss: 3287.0 W
Max Power & Breaker110.85 kW160A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 160A at 300m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1186.11 V (296.53%)0.0 V1956.52 V (489.13%)328704.0 WDrop High
2.5 mm²24 A18 A711.67 V (177.92%)0.0 V1173.91 V (293.48%)197222.4 WDrop High
4 mm²32 A25 A444.79 V (111.2%)0.0 V733.7 V (183.42%)123264.0 WDrop High
6 mm²41 A32 A296.53 V (74.13%)103.5 V489.13 V (122.28%)82176.0 WDrop High
10 mm²57 A44 A177.92 V (44.48%)222.1 V293.48 V (73.37%)49305.6 WDrop High
16 mm²76 A59 A111.2 V (27.8%)288.8 V183.42 V (45.86%)30816.0 WDrop High
25 mm²101 A78 A71.17 V (17.79%)328.8 V117.39 V (29.35%)19722.2 WDrop High
35 mm²125 A97 A50.83 V (12.71%)349.2 V83.85 V (20.96%)14087.3 WDrop High
50 mm²151 A118 A35.58 V (8.9%)364.4 V58.7 V (14.67%)9861.1 WDrop High
70 mm²192 A150 A25.42 V (6.35%)374.6 V41.93 V (10.48%)7043.7 WDrop High
95 mm²232 A181 A18.73 V (4.68%)381.3 V30.89 V (7.72%)5190.1 W~ ≤5%
120 mm²269 A210 A14.83 V (3.71%)385.2 V24.46 V (6.11%)4108.8 W~ ≤5%
150 mm²309 A241 A11.86 V (2.97%)388.1 V19.57 V (4.89%)3287.0 W✓ OK (≤3%)
185 mm²353 A275 A9.62 V (2.4%)390.4 V15.86 V (3.97%)2665.2 W✓ OK (≤3%)
240 mm²415 A324 A7.41 V (1.85%)392.6 V12.23 V (3.06%)2054.4 W✓ OK (≤3%)
300 mm²477 A372 A5.93 V (1.48%)394.1 V9.78 V (2.45%)1643.5 W✓ OK (≤3%)
400 mm²570 A445 A4.45 V (1.11%)395.6 V7.34 V (1.83%)1232.6 W✓ OK (≤3%)

FAQ — Kabelquerschnitt für 160 Ampere bei 300 Meter (400V)

Welcher Kabelquerschnitt wird für 160A bei 300m (400V) benötigt?

Für 160 Ampere über 300 Meter bei 400V wird ein Kupferkabel von 150 mm² empfohlen, um den Spannungsfall unter 3% (11.86V bzw. 2.97%) zu halten.

Wie hoch ist die maximale Leistung bei 160A und 400V?

Die übertragbare Leistung beträgt 110.85 kW bei einer empfohlenen Absicherung von 160A.