⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabelquerschnitt für 175 Ampere bei 200 Meter (400V)

Berechnung des erforderlichen Leiterquerschnitts (mm²) und des Spannungsfalls nach DIN VDE 0100-520 / IEC 60364 für 175 A über 200 m einfache Leitungslänge bei 400V.

Copper Cable (≤3% Drop)120 mm²Drop: 10.81V (2.7%)
Aluminum Cable (≤3% Drop)185 mm²Drop: 11.57V (2.89%)
Voltage at Load389.2 VLine Loss: 3276.9 W
Max Power & Breaker121.24 kW175A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 175A at 200m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A864.87 V (216.22%)0.0 V1426.63 V (356.66%)262150.0 WDrop High
2.5 mm²24 A18 A518.92 V (129.73%)0.0 V855.98 V (213.99%)157290.0 WDrop High
4 mm²32 A25 A324.33 V (81.08%)75.7 V534.99 V (133.75%)98306.2 WDrop High
6 mm²41 A32 A216.22 V (54.05%)183.8 V356.66 V (89.16%)65537.5 WDrop High
10 mm²57 A44 A129.73 V (32.43%)270.3 V213.99 V (53.5%)39322.5 WDrop High
16 mm²76 A59 A81.08 V (20.27%)318.9 V133.75 V (33.44%)24576.6 WDrop High
25 mm²101 A78 A51.89 V (12.97%)348.1 V85.6 V (21.4%)15729.0 WDrop High
35 mm²125 A97 A37.07 V (9.27%)362.9 V61.14 V (15.29%)11235.0 WDrop High
50 mm²151 A118 A25.95 V (6.49%)374.1 V42.8 V (10.7%)7864.5 WDrop High
70 mm²192 A150 A18.53 V (4.63%)381.5 V30.57 V (7.64%)5617.5 W~ ≤5%
95 mm²232 A181 A13.66 V (3.41%)386.3 V22.53 V (5.63%)4139.2 W~ ≤5%
120 mm²269 A210 A10.81 V (2.7%)389.2 V17.83 V (4.46%)3276.9 W✓ OK (≤3%)
150 mm²309 A241 A8.65 V (2.16%)391.4 V14.27 V (3.57%)2621.5 W✓ OK (≤3%)
185 mm²353 A275 A7.01 V (1.75%)393.0 V11.57 V (2.89%)2125.5 W✓ OK (≤3%)
240 mm²415 A324 A5.41 V (1.35%)394.6 V8.92 V (2.23%)1638.4 W✓ OK (≤3%)
300 mm²477 A372 A4.32 V (1.08%)395.7 V7.13 V (1.78%)1310.7 W✓ OK (≤3%)
400 mm²570 A445 A3.24 V (0.81%)396.8 V5.35 V (1.34%)983.1 W✓ OK (≤3%)

FAQ — Kabelquerschnitt für 175 Ampere bei 200 Meter (400V)

Welcher Kabelquerschnitt wird für 175A bei 200m (400V) benötigt?

Für 175 Ampere über 200 Meter bei 400V wird ein Kupferkabel von 120 mm² empfohlen, um den Spannungsfall unter 3% (10.81V bzw. 2.7%) zu halten.

Wie hoch ist die maximale Leistung bei 175A und 400V?

Die übertragbare Leistung beträgt 121.24 kW bei einer empfohlenen Absicherung von 175A.