Kabelquerschnitt für 175 Ampere bei 600 Meter (400V)

Berechnung des erforderlichen Leiterquerschnitts (mm²) und des Spannungsfalls nach DIN VDE 0100-520 / IEC 60364 für 175 A über 600 m einfache Leitungslänge bei 400V.

Copper Cable (≤3% Drop)400 mm²Drop: 9.73V (2.43%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 16.05V (4.01%)
Voltage at Load390.3 VLine Loss: 2949.2 W
Max Power & Breaker121.24 kW175A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 175A at 600m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A2594.61 V (648.65%)0.0 V4279.9 V (1069.97%)786450.0 WDrop High
2.5 mm²24 A18 A1556.77 V (389.19%)0.0 V2567.94 V (641.98%)471870.0 WDrop High
4 mm²32 A25 A972.98 V (243.24%)0.0 V1604.96 V (401.24%)294918.8 WDrop High
6 mm²41 A32 A648.65 V (162.16%)0.0 V1069.97 V (267.49%)196612.5 WDrop High
10 mm²57 A44 A389.19 V (97.3%)10.8 V641.98 V (160.5%)117967.5 WDrop High
16 mm²76 A59 A243.24 V (60.81%)156.8 V401.24 V (100.31%)73729.7 WDrop High
25 mm²101 A78 A155.68 V (38.92%)244.3 V256.79 V (64.2%)47187.0 WDrop High
35 mm²125 A97 A111.2 V (27.8%)288.8 V183.42 V (45.86%)33705.0 WDrop High
50 mm²151 A118 A77.84 V (19.46%)322.2 V128.4 V (32.1%)23593.5 WDrop High
70 mm²192 A150 A55.6 V (13.9%)344.4 V91.71 V (22.93%)16852.5 WDrop High
95 mm²232 A181 A40.97 V (10.24%)359.0 V67.58 V (16.89%)12417.6 WDrop High
120 mm²269 A210 A32.43 V (8.11%)367.6 V53.5 V (13.37%)9830.6 WDrop High
150 mm²309 A241 A25.95 V (6.49%)374.1 V42.8 V (10.7%)7864.5 WDrop High
185 mm²353 A275 A21.04 V (5.26%)379.0 V34.7 V (8.68%)6376.6 WDrop High
240 mm²415 A324 A16.22 V (4.05%)383.8 V26.75 V (6.69%)4915.3 W~ ≤5%
300 mm²477 A372 A12.97 V (3.24%)387.0 V21.4 V (5.35%)3932.2 W~ ≤5%
400 mm²570 A445 A9.73 V (2.43%)390.3 V16.05 V (4.01%)2949.2 W✓ OK (≤3%)

FAQ — Kabelquerschnitt für 175 Ampere bei 600 Meter (400V)

Welcher Kabelquerschnitt wird für 175A bei 600m (400V) benötigt?

Für 175 Ampere über 600 Meter bei 400V wird ein Kupferkabel von 400 mm² empfohlen, um den Spannungsfall unter 3% (9.73V bzw. 2.43%) zu halten.

Wie hoch ist die maximale Leistung bei 175A und 400V?

Die übertragbare Leistung beträgt 121.24 kW bei einer empfohlenen Absicherung von 175A.