Kabelquerschnitt für 225 Ampere bei 10 Meter (400V)

Berechnung des erforderlichen Leiterquerschnitts (mm²) und des Spannungsfalls nach DIN VDE 0100-520 / IEC 60364 für 225 A über 10 m einfache Leitungslänge bei 400V.

Copper Cable (≤3% Drop)95 mm²Drop: 0.88V (0.22%)
Aluminum Cable (≤3% Drop)150 mm²Drop: 0.92V (0.23%)
Voltage at Load399.1 VLine Loss: 342.1 W
Max Power & Breaker155.88 kW225A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 225A at 10m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A55.6 V (13.9%)344.4 V91.71 V (22.93%)21667.5 WDrop High
2.5 mm²24 A18 A33.36 V (8.34%)366.6 V55.03 V (13.76%)13000.5 WDrop High
4 mm²32 A25 A20.85 V (5.21%)379.2 V34.39 V (8.6%)8125.3 WDrop High
6 mm²41 A32 A13.9 V (3.47%)386.1 V22.93 V (5.73%)5416.9 WDrop High
10 mm²57 A44 A8.34 V (2.08%)391.7 V13.76 V (3.44%)3250.1 WDrop High
16 mm²76 A59 A5.21 V (1.3%)394.8 V8.6 V (2.15%)2031.3 WDrop High
25 mm²101 A78 A3.34 V (0.83%)396.7 V5.5 V (1.38%)1300.0 WDrop High
35 mm²125 A97 A2.38 V (0.6%)397.6 V3.93 V (0.98%)928.6 WDrop High
50 mm²151 A118 A1.67 V (0.42%)398.3 V2.75 V (0.69%)650.0 WDrop High
70 mm²192 A150 A1.19 V (0.3%)398.8 V1.97 V (0.49%)464.3 WDrop High
95 mm²232 A181 A0.88 V (0.22%)399.1 V1.45 V (0.36%)342.1 W✓ OK (≤3%)
120 mm²269 A210 A0.69 V (0.17%)399.3 V1.15 V (0.29%)270.8 W✓ OK (≤3%)
150 mm²309 A241 A0.56 V (0.14%)399.4 V0.92 V (0.23%)216.7 W✓ OK (≤3%)
185 mm²353 A275 A0.45 V (0.11%)399.5 V0.74 V (0.19%)175.7 W✓ OK (≤3%)
240 mm²415 A324 A0.35 V (0.09%)399.7 V0.57 V (0.14%)135.4 W✓ OK (≤3%)
300 mm²477 A372 A0.28 V (0.07%)399.7 V0.46 V (0.11%)108.3 W✓ OK (≤3%)
400 mm²570 A445 A0.21 V (0.05%)399.8 V0.34 V (0.09%)81.3 W✓ OK (≤3%)

FAQ — Kabelquerschnitt für 225 Ampere bei 10 Meter (400V)

Welcher Kabelquerschnitt wird für 225A bei 10m (400V) benötigt?

Für 225 Ampere über 10 Meter bei 400V wird ein Kupferkabel von 95 mm² empfohlen, um den Spannungsfall unter 3% (0.88V bzw. 0.22%) zu halten.

Wie hoch ist die maximale Leistung bei 225A und 400V?

Die übertragbare Leistung beträgt 155.88 kW bei einer empfohlenen Absicherung von 225A.