Kabelquerschnitt für 225 Ampere bei 200 Meter (400V)

Berechnung des erforderlichen Leiterquerschnitts (mm²) und des Spannungsfalls nach DIN VDE 0100-520 / IEC 60364 für 225 A über 200 m einfache Leitungslänge bei 400V.

Copper Cable (≤3% Drop)150 mm²Drop: 11.12V (2.78%)
Aluminum Cable (≤3% Drop)240 mm²Drop: 11.46V (2.87%)
Voltage at Load388.9 VLine Loss: 4333.5 W
Max Power & Breaker155.88 kW225A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 225A at 200m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1111.98 V (277.99%)0.0 V1834.24 V (458.56%)433350.0 WDrop High
2.5 mm²24 A18 A667.19 V (166.8%)0.0 V1100.55 V (275.14%)260010.0 WDrop High
4 mm²32 A25 A416.99 V (104.25%)0.0 V687.84 V (171.96%)162506.2 WDrop High
6 mm²41 A32 A277.99 V (69.5%)122.0 V458.56 V (114.64%)108337.5 WDrop High
10 mm²57 A44 A166.8 V (41.7%)233.2 V275.14 V (68.78%)65002.5 WDrop High
16 mm²76 A59 A104.25 V (26.06%)295.8 V171.96 V (42.99%)40626.6 WDrop High
25 mm²101 A78 A66.72 V (16.68%)333.3 V110.05 V (27.51%)26001.0 WDrop High
35 mm²125 A97 A47.66 V (11.91%)352.3 V78.61 V (19.65%)18572.1 WDrop High
50 mm²151 A118 A33.36 V (8.34%)366.6 V55.03 V (13.76%)13000.5 WDrop High
70 mm²192 A150 A23.83 V (5.96%)376.2 V39.31 V (9.83%)9286.1 WDrop High
95 mm²232 A181 A17.56 V (4.39%)382.4 V28.96 V (7.24%)6842.4 W~ ≤5%
120 mm²269 A210 A13.9 V (3.47%)386.1 V22.93 V (5.73%)5416.9 W~ ≤5%
150 mm²309 A241 A11.12 V (2.78%)388.9 V18.34 V (4.59%)4333.5 W✓ OK (≤3%)
185 mm²353 A275 A9.02 V (2.25%)391.0 V14.87 V (3.72%)3513.6 W✓ OK (≤3%)
240 mm²415 A324 A6.95 V (1.74%)393.1 V11.46 V (2.87%)2708.4 W✓ OK (≤3%)
300 mm²477 A372 A5.56 V (1.39%)394.4 V9.17 V (2.29%)2166.8 W✓ OK (≤3%)
400 mm²570 A445 A4.17 V (1.04%)395.8 V6.88 V (1.72%)1625.1 W✓ OK (≤3%)

FAQ — Kabelquerschnitt für 225 Ampere bei 200 Meter (400V)

Welcher Kabelquerschnitt wird für 225A bei 200m (400V) benötigt?

Für 225 Ampere über 200 Meter bei 400V wird ein Kupferkabel von 150 mm² empfohlen, um den Spannungsfall unter 3% (11.12V bzw. 2.78%) zu halten.

Wie hoch ist die maximale Leistung bei 225A und 400V?

Die übertragbare Leistung beträgt 155.88 kW bei einer empfohlenen Absicherung von 225A.