⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabelquerschnitt für 225 Ampere bei 250 Meter (400V)

Berechnung des erforderlichen Leiterquerschnitts (mm²) und des Spannungsfalls nach DIN VDE 0100-520 / IEC 60364 für 225 A über 250 m einfache Leitungslänge bei 400V.

Copper Cable (≤3% Drop)185 mm²Drop: 11.27V (2.82%)
Aluminum Cable (≤3% Drop)300 mm²Drop: 11.46V (2.87%)
Voltage at Load388.7 VLine Loss: 4392.1 W
Max Power & Breaker155.88 kW225A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 225A at 250m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1389.97 V (347.49%)0.0 V2292.8 V (573.2%)541687.5 WDrop High
2.5 mm²24 A18 A833.98 V (208.5%)0.0 V1375.68 V (343.92%)325012.5 WDrop High
4 mm²32 A25 A521.24 V (130.31%)0.0 V859.8 V (214.95%)203132.8 WDrop High
6 mm²41 A32 A347.49 V (86.87%)52.5 V573.2 V (143.3%)135421.9 WDrop High
10 mm²57 A44 A208.5 V (52.12%)191.5 V343.92 V (85.98%)81253.1 WDrop High
16 mm²76 A59 A130.31 V (32.58%)269.7 V214.95 V (53.74%)50783.2 WDrop High
25 mm²101 A78 A83.4 V (20.85%)316.6 V137.57 V (34.39%)32501.2 WDrop High
35 mm²125 A97 A59.57 V (14.89%)340.4 V98.26 V (24.57%)23215.2 WDrop High
50 mm²151 A118 A41.7 V (10.42%)358.3 V68.78 V (17.2%)16250.6 WDrop High
70 mm²192 A150 A29.79 V (7.45%)370.2 V49.13 V (12.28%)11607.6 WDrop High
95 mm²232 A181 A21.95 V (5.49%)378.1 V36.2 V (9.05%)8553.0 WDrop High
120 mm²269 A210 A17.37 V (4.34%)382.6 V28.66 V (7.17%)6771.1 W~ ≤5%
150 mm²309 A241 A13.9 V (3.47%)386.1 V22.93 V (5.73%)5416.9 W~ ≤5%
185 mm²353 A275 A11.27 V (2.82%)388.7 V18.59 V (4.65%)4392.1 W✓ OK (≤3%)
240 mm²415 A324 A8.69 V (2.17%)391.3 V14.33 V (3.58%)3385.5 W✓ OK (≤3%)
300 mm²477 A372 A6.95 V (1.74%)393.1 V11.46 V (2.87%)2708.4 W✓ OK (≤3%)
400 mm²570 A445 A5.21 V (1.3%)394.8 V8.6 V (2.15%)2031.3 W✓ OK (≤3%)

FAQ — Kabelquerschnitt für 225 Ampere bei 250 Meter (400V)

Welcher Kabelquerschnitt wird für 225A bei 250m (400V) benötigt?

Für 225 Ampere über 250 Meter bei 400V wird ein Kupferkabel von 185 mm² empfohlen, um den Spannungsfall unter 3% (11.27V bzw. 2.82%) zu halten.

Wie hoch ist die maximale Leistung bei 225A und 400V?

Die übertragbare Leistung beträgt 155.88 kW bei einer empfohlenen Absicherung von 225A.