Kabelquerschnitt für 275 Ampere bei 300 Meter (400V)

Berechnung des erforderlichen Leiterquerschnitts (mm²) und des Spannungsfalls nach DIN VDE 0100-520 / IEC 60364 für 275 A über 300 m einfache Leitungslänge bei 400V.

Copper Cable (≤3% Drop)300 mm²Drop: 10.19V (2.55%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 12.61V (3.15%)
Voltage at Load389.8 VLine Loss: 4855.1 W
Max Power & Breaker190.53 kW300A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 275A at 300m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A2038.62 V (509.66%)0.0 V3362.78 V (840.69%)971025.0 WDrop High
2.5 mm²24 A18 A1223.17 V (305.79%)0.0 V2017.67 V (504.42%)582615.0 WDrop High
4 mm²32 A25 A764.48 V (191.12%)0.0 V1261.04 V (315.26%)364134.4 WDrop High
6 mm²41 A32 A509.66 V (127.41%)0.0 V840.69 V (210.17%)242756.2 WDrop High
10 mm²57 A44 A305.79 V (76.45%)94.2 V504.42 V (126.1%)145653.8 WDrop High
16 mm²76 A59 A191.12 V (47.78%)208.9 V315.26 V (78.82%)91033.6 WDrop High
25 mm²101 A78 A122.32 V (30.58%)277.7 V201.77 V (50.44%)58261.5 WDrop High
35 mm²125 A97 A87.37 V (21.84%)312.6 V144.12 V (36.03%)41615.4 WDrop High
50 mm²151 A118 A61.16 V (15.29%)338.8 V100.88 V (25.22%)29130.7 WDrop High
70 mm²192 A150 A43.68 V (10.92%)356.3 V72.06 V (18.01%)20807.7 WDrop High
95 mm²232 A181 A32.19 V (8.05%)367.8 V53.1 V (13.27%)15332.0 WDrop High
120 mm²269 A210 A25.48 V (6.37%)374.5 V42.03 V (10.51%)12137.8 WDrop High
150 mm²309 A241 A20.39 V (5.1%)379.6 V33.63 V (8.41%)9710.2 WDrop High
185 mm²353 A275 A16.53 V (4.13%)383.5 V27.27 V (6.82%)7873.2 W~ ≤5%
240 mm²415 A324 A12.74 V (3.19%)387.3 V21.02 V (5.25%)6068.9 W~ ≤5%
300 mm²477 A372 A10.19 V (2.55%)389.8 V16.81 V (4.2%)4855.1 W✓ OK (≤3%)
400 mm²570 A445 A7.64 V (1.91%)392.4 V12.61 V (3.15%)3641.3 W✓ OK (≤3%)

FAQ — Kabelquerschnitt für 275 Ampere bei 300 Meter (400V)

Welcher Kabelquerschnitt wird für 275A bei 300m (400V) benötigt?

Für 275 Ampere über 300 Meter bei 400V wird ein Kupferkabel von 300 mm² empfohlen, um den Spannungsfall unter 3% (10.19V bzw. 2.55%) zu halten.

Wie hoch ist die maximale Leistung bei 275A und 400V?

Die übertragbare Leistung beträgt 190.53 kW bei einer empfohlenen Absicherung von 300A.