⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-25)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabelquerschnitt für 350 Ampere bei 300 Meter (400V)

Berechnung des erforderlichen Leiterquerschnitts (mm²) und des Spannungsfalls nach DIN VDE 0100-520 / IEC 60364 für 350 A über 300 m einfache Leitungslänge bei 400V.

Copper Cable (≤3% Drop)400 mm²Drop: 9.73V (2.43%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 16.05V (4.01%)
Voltage at Load390.3 VLine Loss: 5898.4 W
Max Power & Breaker242.49 kW350A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 350A at 300m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A2594.61 V (648.65%)0.0 V4279.9 V (1069.97%)1572900.0 WDrop High
2.5 mm²24 A18 A1556.77 V (389.19%)0.0 V2567.94 V (641.98%)943740.0 WDrop High
4 mm²32 A25 A972.98 V (243.24%)0.0 V1604.96 V (401.24%)589837.5 WDrop High
6 mm²41 A32 A648.65 V (162.16%)0.0 V1069.97 V (267.49%)393225.0 WDrop High
10 mm²57 A44 A389.19 V (97.3%)10.8 V641.98 V (160.5%)235935.0 WDrop High
16 mm²76 A59 A243.24 V (60.81%)156.8 V401.24 V (100.31%)147459.4 WDrop High
25 mm²101 A78 A155.68 V (38.92%)244.3 V256.79 V (64.2%)94374.0 WDrop High
35 mm²125 A97 A111.2 V (27.8%)288.8 V183.42 V (45.86%)67410.0 WDrop High
50 mm²151 A118 A77.84 V (19.46%)322.2 V128.4 V (32.1%)47187.0 WDrop High
70 mm²192 A150 A55.6 V (13.9%)344.4 V91.71 V (22.93%)33705.0 WDrop High
95 mm²232 A181 A40.97 V (10.24%)359.0 V67.58 V (16.89%)24835.3 WDrop High
120 mm²269 A210 A32.43 V (8.11%)367.6 V53.5 V (13.37%)19661.2 WDrop High
150 mm²309 A241 A25.95 V (6.49%)374.1 V42.8 V (10.7%)15729.0 WDrop High
185 mm²353 A275 A21.04 V (5.26%)379.0 V34.7 V (8.68%)12753.2 WDrop High
240 mm²415 A324 A16.22 V (4.05%)383.8 V26.75 V (6.69%)9830.6 W~ ≤5%
300 mm²477 A372 A12.97 V (3.24%)387.0 V21.4 V (5.35%)7864.5 W~ ≤5%
400 mm²570 A445 A9.73 V (2.43%)390.3 V16.05 V (4.01%)5898.4 W✓ OK (≤3%)

FAQ — Kabelquerschnitt für 350 Ampere bei 300 Meter (400V)

Welcher Kabelquerschnitt wird für 350A bei 300m (400V) benötigt?

Für 350 Ampere über 300 Meter bei 400V wird ein Kupferkabel von 400 mm² empfohlen, um den Spannungsfall unter 3% (9.73V bzw. 2.43%) zu halten.

Wie hoch ist die maximale Leistung bei 350A und 400V?

Die übertragbare Leistung beträgt 242.49 kW bei einer empfohlenen Absicherung von 350A.