Kabelquerschnitt für 45 Ampere bei 120 Meter (400V)

Berechnung des erforderlichen Leiterquerschnitts (mm²) und des Spannungsfalls nach DIN VDE 0100-520 / IEC 60364 für 45 A über 120 m einfache Leitungslänge bei 400V.

Copper Cable (≤3% Drop)25 mm²Drop: 8.01V (2.0%)
Aluminum Cable (≤3% Drop)35 mm²Drop: 9.43V (2.36%)
Voltage at Load392.0 VLine Loss: 624.0 W
Max Power & Breaker31.18 kW45A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 45A at 120m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A133.44 V (33.36%)266.6 V220.11 V (55.03%)10400.4 WDrop High
2.5 mm²24 A18 A80.06 V (20.02%)319.9 V132.07 V (33.02%)6240.2 WDrop High
4 mm²32 A25 A50.04 V (12.51%)350.0 V82.54 V (20.64%)3900.2 WDrop High
6 mm²41 A32 A33.36 V (8.34%)366.6 V55.03 V (13.76%)2600.1 WDrop High
10 mm²57 A44 A20.02 V (5.0%)380.0 V33.02 V (8.25%)1560.1 WDrop High
16 mm²76 A59 A12.51 V (3.13%)387.5 V20.64 V (5.16%)975.0 W~ ≤5%
25 mm²101 A78 A8.01 V (2.0%)392.0 V13.21 V (3.3%)624.0 W✓ OK (≤3%)
35 mm²125 A97 A5.72 V (1.43%)394.3 V9.43 V (2.36%)445.7 W✓ OK (≤3%)
50 mm²151 A118 A4.0 V (1.0%)396.0 V6.6 V (1.65%)312.0 W✓ OK (≤3%)
70 mm²192 A150 A2.86 V (0.71%)397.1 V4.72 V (1.18%)222.9 W✓ OK (≤3%)
95 mm²232 A181 A2.11 V (0.53%)397.9 V3.48 V (0.87%)164.2 W✓ OK (≤3%)
120 mm²269 A210 A1.67 V (0.42%)398.3 V2.75 V (0.69%)130.0 W✓ OK (≤3%)
150 mm²309 A241 A1.33 V (0.33%)398.7 V2.2 V (0.55%)104.0 W✓ OK (≤3%)
185 mm²353 A275 A1.08 V (0.27%)398.9 V1.78 V (0.45%)84.3 W✓ OK (≤3%)
240 mm²415 A324 A0.83 V (0.21%)399.2 V1.38 V (0.34%)65.0 W✓ OK (≤3%)
300 mm²477 A372 A0.67 V (0.17%)399.3 V1.1 V (0.28%)52.0 W✓ OK (≤3%)
400 mm²570 A445 A0.5 V (0.13%)399.5 V0.83 V (0.21%)39.0 W✓ OK (≤3%)

FAQ — Kabelquerschnitt für 45 Ampere bei 120 Meter (400V)

Welcher Kabelquerschnitt wird für 45A bei 120m (400V) benötigt?

Für 45 Ampere über 120 Meter bei 400V wird ein Kupferkabel von 25 mm² empfohlen, um den Spannungsfall unter 3% (8.01V bzw. 2.0%) zu halten.

Wie hoch ist die maximale Leistung bei 45A und 400V?

Die übertragbare Leistung beträgt 31.18 kW bei einer empfohlenen Absicherung von 45A.