Kabelquerschnitt für 475 Ampere bei 120 Meter (400V)

Berechnung des erforderlichen Leiterquerschnitts (mm²) und des Spannungsfalls nach DIN VDE 0100-520 / IEC 60364 für 475 A über 120 m einfache Leitungslänge bei 400V.

Copper Cable (≤3% Drop)300 mm²Drop: 7.04V (1.76%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 8.71V (2.18%)
Voltage at Load393.0 VLine Loss: 5794.1 W
Max Power & Breaker329.09 kW500A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 475A at 120m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1408.5 V (352.13%)0.0 V2323.37 V (580.84%)1158810.0 WDrop High
2.5 mm²24 A18 A845.1 V (211.28%)0.0 V1394.02 V (348.51%)695286.0 WDrop High
4 mm²32 A25 A528.19 V (132.05%)0.0 V871.26 V (217.82%)434553.8 WDrop High
6 mm²41 A32 A352.13 V (88.03%)47.9 V580.84 V (145.21%)289702.5 WDrop High
10 mm²57 A44 A211.28 V (52.82%)188.7 V348.51 V (87.13%)173821.5 WDrop High
16 mm²76 A59 A132.05 V (33.01%)268.0 V217.82 V (54.45%)108638.4 WDrop High
25 mm²101 A78 A84.51 V (21.13%)315.5 V139.4 V (34.85%)69528.6 WDrop High
35 mm²125 A97 A60.36 V (15.09%)339.6 V99.57 V (24.89%)49663.3 WDrop High
50 mm²151 A118 A42.26 V (10.56%)357.7 V69.7 V (17.43%)34764.3 WDrop High
70 mm²192 A150 A30.18 V (7.55%)369.8 V49.79 V (12.45%)24831.6 WDrop High
95 mm²232 A181 A22.24 V (5.56%)377.8 V36.68 V (9.17%)18297.0 WDrop High
120 mm²269 A210 A17.61 V (4.4%)382.4 V29.04 V (7.26%)14485.1 WDrop High
150 mm²309 A241 A14.09 V (3.52%)385.9 V23.23 V (5.81%)11588.1 WDrop High
185 mm²353 A275 A11.42 V (2.86%)388.6 V18.84 V (4.71%)9395.8 WDrop High
240 mm²415 A324 A8.8 V (2.2%)391.2 V14.52 V (3.63%)7242.6 WDrop High
300 mm²477 A372 A7.04 V (1.76%)393.0 V11.62 V (2.9%)5794.1 W✓ OK (≤3%)
400 mm²570 A445 A5.28 V (1.32%)394.7 V8.71 V (2.18%)4345.5 W✓ OK (≤3%)

FAQ — Kabelquerschnitt für 475 Ampere bei 120 Meter (400V)

Welcher Kabelquerschnitt wird für 475A bei 120m (400V) benötigt?

Für 475 Ampere über 120 Meter bei 400V wird ein Kupferkabel von 300 mm² empfohlen, um den Spannungsfall unter 3% (7.04V bzw. 1.76%) zu halten.

Wie hoch ist die maximale Leistung bei 475A und 400V?

Die übertragbare Leistung beträgt 329.09 kW bei einer empfohlenen Absicherung von 500A.