⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabelquerschnitt für 500 Ampere bei 500 Meter (400V)

Berechnung des erforderlichen Leiterquerschnitts (mm²) und des Spannungsfalls nach DIN VDE 0100-520 / IEC 60364 für 500 A über 500 m einfache Leitungslänge bei 400V.

Copper Cable (≤3% Drop)2× 400 mm²Drop: 11.59V (2.9%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 38.21V (9.55%)
Voltage at Load388.4 VLine Loss: 10031.2 W
Max Power & Breaker346.41 kW500A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 500A at 500m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A6177.65 V (1544.41%)0.0 V10190.23 V (2547.56%)5350000.0 WDrop High
2.5 mm²24 A18 A3706.59 V (926.65%)0.0 V6114.14 V (1528.53%)3210000.0 WDrop High
4 mm²32 A25 A2316.62 V (579.15%)0.0 V3821.34 V (955.33%)2006250.0 WDrop High
6 mm²41 A32 A1544.41 V (386.1%)0.0 V2547.56 V (636.89%)1337500.0 WDrop High
10 mm²57 A44 A926.65 V (231.66%)0.0 V1528.53 V (382.13%)802500.0 WDrop High
16 mm²76 A59 A579.15 V (144.79%)0.0 V955.33 V (238.83%)501562.5 WDrop High
25 mm²101 A78 A370.66 V (92.66%)29.3 V611.41 V (152.85%)321000.0 WDrop High
35 mm²125 A97 A264.76 V (66.19%)135.2 V436.72 V (109.18%)229285.7 WDrop High
50 mm²151 A118 A185.33 V (46.33%)214.7 V305.71 V (76.43%)160500.0 WDrop High
70 mm²192 A150 A132.38 V (33.09%)267.6 V218.36 V (54.59%)114642.9 WDrop High
95 mm²232 A181 A97.54 V (24.39%)302.5 V160.9 V (40.22%)84473.7 WDrop High
120 mm²269 A210 A77.22 V (19.31%)322.8 V127.38 V (31.84%)66875.0 WDrop High
150 mm²309 A241 A61.78 V (15.44%)338.2 V101.9 V (25.48%)53500.0 WDrop High
185 mm²353 A275 A50.09 V (12.52%)349.9 V82.62 V (20.66%)43378.4 WDrop High
240 mm²415 A324 A38.61 V (9.65%)361.4 V63.69 V (15.92%)33437.5 WDrop High
300 mm²477 A372 A30.89 V (7.72%)369.1 V50.95 V (12.74%)26750.0 WDrop High
400 mm²570 A445 A23.17 V (5.79%)376.8 V38.21 V (9.55%)20062.5 WDrop High

FAQ — Kabelquerschnitt für 500 Ampere bei 500 Meter (400V)

Welcher Kabelquerschnitt wird für 500A bei 500m (400V) benötigt?

Für 500 Ampere über 500 Meter bei 400V wird ein Kupferkabel von 2× 400 mm² empfohlen, um den Spannungsfall unter 3% (11.59V bzw. 2.9%) zu halten.

Wie hoch ist die maximale Leistung bei 500A und 400V?

Die übertragbare Leistung beträgt 346.41 kW bei einer empfohlenen Absicherung von 500A.