⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabelarea för 100 Ampere vid 25 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 100 A över 25 m vid 230V.

Copper Cable (≤3% Drop)25 mm²Drop: 4.28V (1.86%)
Aluminum Cable (≤3% Drop)50 mm²Drop: 3.53V (1.53%)
Voltage at Load225.7 VLine Loss: 428.0 W
Max Power & Breaker23.0 kW100A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 100A at 25m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A71.33 V (31.01%)158.7 V117.67 V (51.16%)7133.3 WDrop High
2.5 mm²24 A18 A42.8 V (18.61%)187.2 V70.6 V (30.7%)4280.0 WDrop High
4 mm²32 A25 A26.75 V (11.63%)203.2 V44.12 V (19.18%)2675.0 WDrop High
6 mm²41 A32 A17.83 V (7.75%)212.2 V29.42 V (12.79%)1783.3 WDrop High
10 mm²57 A44 A10.7 V (4.65%)219.3 V17.65 V (7.67%)1070.0 WDrop High
16 mm²76 A59 A6.69 V (2.91%)223.3 V11.03 V (4.8%)668.7 WDrop High
25 mm²101 A78 A4.28 V (1.86%)225.7 V7.06 V (3.07%)428.0 W✓ OK (≤3%)
35 mm²125 A97 A3.06 V (1.33%)226.9 V5.04 V (2.19%)305.7 W✓ OK (≤3%)
50 mm²151 A118 A2.14 V (0.93%)227.9 V3.53 V (1.53%)214.0 W✓ OK (≤3%)
70 mm²192 A150 A1.53 V (0.66%)228.5 V2.52 V (1.1%)152.9 W✓ OK (≤3%)
95 mm²232 A181 A1.13 V (0.49%)228.9 V1.86 V (0.81%)112.6 W✓ OK (≤3%)
120 mm²269 A210 A0.89 V (0.39%)229.1 V1.47 V (0.64%)89.2 W✓ OK (≤3%)
150 mm²309 A241 A0.71 V (0.31%)229.3 V1.18 V (0.51%)71.3 W✓ OK (≤3%)
185 mm²353 A275 A0.58 V (0.25%)229.4 V0.95 V (0.41%)57.8 W✓ OK (≤3%)
240 mm²415 A324 A0.45 V (0.19%)229.6 V0.74 V (0.32%)44.6 W✓ OK (≤3%)
300 mm²477 A372 A0.36 V (0.16%)229.6 V0.59 V (0.26%)35.7 W✓ OK (≤3%)
400 mm²570 A445 A0.27 V (0.12%)229.7 V0.44 V (0.19%)26.7 W✓ OK (≤3%)

FAQ — Kabelarea för 100 Ampere vid 25 Meter (230V)

Vilken kabelarea krävs för 100A vid 25 meter (230V)?

För 100 Ampere över 25 meter vid 230V rekommenderas 25 mm² kopparkabel för att hålla spänningsfallet under 3% (4.28V / 1.86%).

Hur stor effekt motsvarar 100A vid 230V?

Det motsvarar 23.0 kW med en rekommenderad säkring på 100A.