Kabelarea för 16 Ampere vid 25 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 16 A över 25 m vid 230V.

Copper Cable (≤3% Drop)2.5 mm²Drop: 6.85V (2.98%)
Aluminum Cable (≤3% Drop)6 mm²Drop: 4.71V (2.05%)
Voltage at Load223.2 VLine Loss: 109.6 W
Max Power & Breaker3.68 kW16A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 16A at 25m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A11.41 V (4.96%)218.6 V18.83 V (8.19%)182.6 W~ ≤5%
2.5 mm²24 A18 A6.85 V (2.98%)223.2 V11.3 V (4.91%)109.6 W✓ OK (≤3%)
4 mm²32 A25 A4.28 V (1.86%)225.7 V7.06 V (3.07%)68.5 W✓ OK (≤3%)
6 mm²41 A32 A2.85 V (1.24%)227.1 V4.71 V (2.05%)45.7 W✓ OK (≤3%)
10 mm²57 A44 A1.71 V (0.74%)228.3 V2.82 V (1.23%)27.4 W✓ OK (≤3%)
16 mm²76 A59 A1.07 V (0.47%)228.9 V1.76 V (0.77%)17.1 W✓ OK (≤3%)
25 mm²101 A78 A0.68 V (0.3%)229.3 V1.13 V (0.49%)11.0 W✓ OK (≤3%)
35 mm²125 A97 A0.49 V (0.21%)229.5 V0.81 V (0.35%)7.8 W✓ OK (≤3%)
50 mm²151 A118 A0.34 V (0.15%)229.7 V0.56 V (0.25%)5.5 W✓ OK (≤3%)
70 mm²192 A150 A0.24 V (0.11%)229.8 V0.4 V (0.18%)3.9 W✓ OK (≤3%)
95 mm²232 A181 A0.18 V (0.08%)229.8 V0.3 V (0.13%)2.9 W✓ OK (≤3%)
120 mm²269 A210 A0.14 V (0.06%)229.9 V0.24 V (0.1%)2.3 W✓ OK (≤3%)
150 mm²309 A241 A0.11 V (0.05%)229.9 V0.19 V (0.08%)1.8 W✓ OK (≤3%)
185 mm²353 A275 A0.09 V (0.04%)229.9 V0.15 V (0.07%)1.5 W✓ OK (≤3%)
240 mm²415 A324 A0.07 V (0.03%)229.9 V0.12 V (0.05%)1.1 W✓ OK (≤3%)
300 mm²477 A372 A0.06 V (0.02%)229.9 V0.09 V (0.04%)0.9 W✓ OK (≤3%)
400 mm²570 A445 A0.04 V (0.02%)230.0 V0.07 V (0.03%)0.7 W✓ OK (≤3%)

FAQ — Kabelarea för 16 Ampere vid 25 Meter (230V)

Vilken kabelarea krävs för 16A vid 25 meter (230V)?

För 16 Ampere över 25 meter vid 230V rekommenderas 2.5 mm² kopparkabel för att hålla spänningsfallet under 3% (6.85V / 2.98%).

Hur stor effekt motsvarar 16A vid 230V?

Det motsvarar 3.68 kW med en rekommenderad säkring på 16A.