Kabelarea för 110 Ampere vid 40 Meter (400V)
Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 110 A över 40 m vid 400V.
Copper Cable (≤3% Drop)35 mm²Drop: 4.66V (1.16%)
Aluminum Cable (≤3% Drop)50 mm²Drop: 5.38V (1.35%)
Voltage at Load395.3 VLine Loss: 887.8 W
Max Power & Breaker76.21 kW110A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 110A at 40m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 108.73 V (27.18%) | 291.3 V | 179.35 V (44.84%) | 20715.2 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 65.24 V (16.31%) | 334.8 V | 107.61 V (26.9%) | 12429.1 W | Drop High |
| 4 mm² | 32 A | 25 A | 40.77 V (10.19%) | 359.2 V | 67.26 V (16.81%) | 7768.2 W | Drop High |
| 6 mm² | 41 A | 32 A | 27.18 V (6.8%) | 372.8 V | 44.84 V (11.21%) | 5178.8 W | Drop High |
| 10 mm² | 57 A | 44 A | 16.31 V (4.08%) | 383.7 V | 26.9 V (6.73%) | 3107.3 W | Drop High |
| 16 mm² | 76 A | 59 A | 10.19 V (2.55%) | 389.8 V | 16.81 V (4.2%) | 1942.0 W | Drop High |
| 25 mm² | 101 A | 78 A | 6.52 V (1.63%) | 393.5 V | 10.76 V (2.69%) | 1242.9 W | Drop High |
| 35 mm² | 125 A | 97 A | 4.66 V (1.16%) | 395.3 V | 7.69 V (1.92%) | 887.8 W | ✓ OK (≤3%) |
| 50 mm² | 151 A | 118 A | 3.26 V (0.82%) | 396.7 V | 5.38 V (1.35%) | 621.5 W | ✓ OK (≤3%) |
| 70 mm² | 192 A | 150 A | 2.33 V (0.58%) | 397.7 V | 3.84 V (0.96%) | 443.9 W | ✓ OK (≤3%) |
| 95 mm² | 232 A | 181 A | 1.72 V (0.43%) | 398.3 V | 2.83 V (0.71%) | 327.1 W | ✓ OK (≤3%) |
| 120 mm² | 269 A | 210 A | 1.36 V (0.34%) | 398.6 V | 2.24 V (0.56%) | 258.9 W | ✓ OK (≤3%) |
| 150 mm² | 309 A | 241 A | 1.09 V (0.27%) | 398.9 V | 1.79 V (0.45%) | 207.2 W | ✓ OK (≤3%) |
| 185 mm² | 353 A | 275 A | 0.88 V (0.22%) | 399.1 V | 1.45 V (0.36%) | 168.0 W | ✓ OK (≤3%) |
| 240 mm² | 415 A | 324 A | 0.68 V (0.17%) | 399.3 V | 1.12 V (0.28%) | 129.5 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 0.54 V (0.14%) | 399.5 V | 0.9 V (0.22%) | 103.6 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 0.41 V (0.1%) | 399.6 V | 0.67 V (0.17%) | 77.7 W | ✓ OK (≤3%) |
FAQ — Kabelarea för 110 Ampere vid 40 Meter (400V)
Vilken kabelarea krävs för 110A vid 40 meter (400V)?
För 110 Ampere över 40 meter vid 400V rekommenderas 35 mm² kopparkabel för att hålla spänningsfallet under 3% (4.66V / 1.16%).
Hur stor effekt motsvarar 110A vid 400V?
Det motsvarar 76.21 kW med en rekommenderad säkring på 110A.
Related Lengths & Currents (400V)
110A · 5m (400V)110A · 10m (400V)110A · 15m (400V)110A · 20m (400V)110A · 25m (400V)110A · 30m (400V)110A · 35m (400V)110A · 45m (400V)110A · 50m (400V)110A · 60m (400V)110A · 70m (400V)10A · 40m (400V)16A · 40m (400V)20A · 40m (400V)25A · 40m (400V)32A · 40m (400V)40A · 40m (400V)50A · 40m (400V)63A · 40m (400V)80A · 40m (400V)100A · 40m (400V)125A · 40m (400V)160A · 40m (400V)200A · 40m (400V)