Kabelarea för 110 Ampere vid 60 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 110 A över 60 m vid 400V.

Copper Cable (≤3% Drop)35 mm²Drop: 6.99V (1.75%)
Aluminum Cable (≤3% Drop)50 mm²Drop: 8.07V (2.02%)
Voltage at Load393.0 VLine Loss: 1331.7 W
Max Power & Breaker76.21 kW110A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 110A at 60m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A163.09 V (40.77%)236.9 V269.02 V (67.26%)31072.8 WDrop High
2.5 mm²24 A18 A97.85 V (24.46%)302.1 V161.41 V (40.35%)18643.7 WDrop High
4 mm²32 A25 A61.16 V (15.29%)338.8 V100.88 V (25.22%)11652.3 WDrop High
6 mm²41 A32 A40.77 V (10.19%)359.2 V67.26 V (16.81%)7768.2 WDrop High
10 mm²57 A44 A24.46 V (6.12%)375.5 V40.35 V (10.09%)4660.9 WDrop High
16 mm²76 A59 A15.29 V (3.82%)384.7 V25.22 V (6.31%)2913.1 WDrop High
25 mm²101 A78 A9.79 V (2.45%)390.2 V16.14 V (4.04%)1864.4 WDrop High
35 mm²125 A97 A6.99 V (1.75%)393.0 V11.53 V (2.88%)1331.7 W✓ OK (≤3%)
50 mm²151 A118 A4.89 V (1.22%)395.1 V8.07 V (2.02%)932.2 W✓ OK (≤3%)
70 mm²192 A150 A3.49 V (0.87%)396.5 V5.76 V (1.44%)665.8 W✓ OK (≤3%)
95 mm²232 A181 A2.58 V (0.64%)397.4 V4.25 V (1.06%)490.6 W✓ OK (≤3%)
120 mm²269 A210 A2.04 V (0.51%)398.0 V3.36 V (0.84%)388.4 W✓ OK (≤3%)
150 mm²309 A241 A1.63 V (0.41%)398.4 V2.69 V (0.67%)310.7 W✓ OK (≤3%)
185 mm²353 A275 A1.32 V (0.33%)398.7 V2.18 V (0.55%)251.9 W✓ OK (≤3%)
240 mm²415 A324 A1.02 V (0.25%)399.0 V1.68 V (0.42%)194.2 W✓ OK (≤3%)
300 mm²477 A372 A0.82 V (0.2%)399.2 V1.35 V (0.34%)155.4 W✓ OK (≤3%)
400 mm²570 A445 A0.61 V (0.15%)399.4 V1.01 V (0.25%)116.5 W✓ OK (≤3%)

FAQ — Kabelarea för 110 Ampere vid 60 Meter (400V)

Vilken kabelarea krävs för 110A vid 60 meter (400V)?

För 110 Ampere över 60 meter vid 400V rekommenderas 35 mm² kopparkabel för att hålla spänningsfallet under 3% (6.99V / 1.75%).

Hur stor effekt motsvarar 110A vid 400V?

Det motsvarar 76.21 kW med en rekommenderad säkring på 110A.